Operating instructions

10 GALAXY
CLEAN STEAM BOILER SYSTEM
A. Fill the boiler to water line indicated on the boiler.
B. Follow start-up procedure for boiler and operate the boiler
with steam in the entire system for 2 or 3 days to bring oil
and dirt from the system to the boiler. While system is in
operation, maintain the proper water level in the boiler by
slowly adding water to the boiler.
C. Shut down burner, cool down boiler and drain system.
D. Procedure to dissolve oil and grease in boiler:
1. Fill boiler to proper water line.
2. Prepare a boil-out solution of sodium hydroxide
(caustic soda) and tri-sodium phosphate:
NOTE: Use CAUTION in handling chemicals. Caustic
soda is harmful to skin, eyes and clothing.
(a)Proportions: 1 kg of each chemical per 465 L
(1 lb/50 U.S. gallons) of system water.
(b)Stir chemicals into water until dissolved and pour into
the boiler through a top tapping. Replace plug.
3. Start the burner; boil the water for at least 5 hours; shut
off the burner.
E. With CAUTION, drain the boiler solution to a safe location.
DO NOT LEAVE SOLUTION SITTING IN SYSTEM OVER 2
HOURS.
F. Wash the water side of the boiler thoroughly using a high
pressure water stream. Fill and drain the boiler several
times.
TREATING WATER FOR CORROSION CONTROL
(This is not scale control.)
A. Prepare a solution of sodium chromate.
Proportions: 1 kg of chemical per 465 L (1 lb./50 U.S.
gallons) of boiler water.
B. Stir chemical in water until dissolved and pour into boiler
through a top tapping. Replace plug.
FILLING AND VENTING THE STEAM BOILER
A.Refill the boiler to the indicated water line.
B.Bring water to boiling temperature, promptly.
C.The boiler is now ready to be put into service or on stand-
by.
INITIAL START
Safe lighting and other performance criteria were met when
testing various gas manifold and control assemblies used
on the Galaxy Series boilers under the ANSI Z21.13b-1994
or CSA B149.1-00 for natural gas and propane.
INSTRUCTIONS
Follow the lighting instructions in this manual that apply to the par-
ticular ignition system equipped on this boiler. (Also, see figures on
page 2 for location of gas manifold, gas valve and control assem-
bly.) These instructions are also attached to the boiler.
1. Continuous Burning Pilot (24V).
FOR BOILERS EQUIPPED WITH WHITE RODGERS 36C
A. This appliance has a pilot that must be lighted by hand. When
lighting the pilot, follow these instructions exactly.
B. BEFORE LIGHTING, smell all around the appliance area for gas.
Be sure to smell next to the floor because some gas is heavier
than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not use any phone in your
building.
Immediately call your gas supplier from a neighbor's phone.
Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob. Never
use tools. If the knob will not push in or turn by hand, don’t try to
repair it; call a qualified service technician. Force or attempted
repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the appli-
ance and to replace any part of the control system and any gas
control that has been under water.
Lighting Instructions
1. STOP! Read the safety information above.
2. Set the thermostat to lowest setting.
3. Turn off all electrical power to the appliance.
4. Depress gas control knob slightly and turn clockwise
to OFF. If knob is in ON turn clockwise to PILOT
(then depress knob slightly and turn clockwise to OFF.
NOTE: Knob cannot be turned from PILOT to
OFF unless knob is depressed slightly. Do
not use tools or excessive force.
5. Wait five (5) minutes to clear out any gas. If you
then smell gas, STOP! Follow B in the safety
information above.
If you don’t smell gas, go to next
step.
6. Remove the base burner
access panel(s) located
under the gas control unit.
7. Find pilot—follow small metal tubes from gas control.
The pilot is
between two burner tubes behind the burner access panel.
8. Turn knob on gas control counterclockwise to PILOT.
9. Depress control knob all the way and hold in. Immediately light the
pilot with a match. Continue to hold the control knob down for about
one (1) minute after the pilot is lit. Release knob and it will pop back
up. Pilot should remain lit. If it goes out, repeat steps 4, 5,
8, and 9.
If knob does not pop up when released, turn
clockwise. to OFF, stop and immedi-
ately call your service technician or gas sup-
plier.
• If the pilot will not stay lit after several tries, turn the gas control
knob to OFF and call your service technician or gas supplier.
10. Replace base burner access panel(s).
11. Turn gas control knob counterclockwise to ON.
12. Turn on all electrical power to the appliance.
13. Set thermostat to desired setting.
To Turn Off Gas To Appliance
1. Set the thermostat to lowest setting.
2. Turn off all electrical power to the appliance if service is to be per-
formed.
3. Turn gas control knob clockwise to PILOT.
4. Depress gas control knob slightly and turn clockwise to
OFF. Do not use tools or excessive force.
SAFETY INFORMATION
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly,
a fire or explosion may result causing property damage, per-
sonal injury or loss of life.