Specifications

48
THE 4/20 mA MENU
FR1 4/20 SELECT
The user may select which parameter the 4-20 mA analog output represents for FR1. Choices are
Flame QUALITY or Flame SIGNAL. Factory default is Flame QUALITY. Press SELECT to enter
option; Use UP or DOWN key to pick Flame QUALITY or Flame SIGNAL; press PROGRAM to
SAVE.
FR1 20mA MAP VAL (Range)
This option allows the user to select the 4-20 mA range (MAP VAL) of the parameter selected above.
If Flame QUALITY was selected, the analog output will be 4 mA when the FQ=0. The range, or
Flame Quality value for 20 mA (20mA MAP VAL), is user selectable anywhere between 40 and 100.
The factory default value is 100 (see Example 1 below). If the user selects a value of 50, when the
Flame Quality reaches 50, the analog output will be 20 mA (see Example 2 below).
If Flame SIGNAL was selected, the analog output will be 4 mA when the flame signal is 000. The
range, or Flame Signal value for 20 mA (20mA MAP VAL), is user selectable anywhere between 400
and 999. The factory default is 999. If the user selects a MAP VAL of 500, when the Flame Signal
reaches 500, the analog output will be at 20 mA.
Press SELECT to enter option and then use UP or DOWN key to pick MAP Value (between 40-100
for FQ, or between 400-999 for FS), then press PROGRAM to SAVE.
FR2 4/20 SELECT
The user may select which parameter the 4-20 mA analog output represents for FR2. Choices are
Flame QUALITY or Flame SIGNAL. The factory default is Flame QUALITY. Press SELECT to
enter option; Use UP or DOWN key to pick Flame QUALITY or Flame SIGNAL; press PROGRAM
to SAVE.
FR2 20mA MAP VAL (Range)
This option allows the user to select the 4-20 mA range (MAP VAL) of the parameter selected above.
If Flame QUALITY was selected, the analog output will be 4 mA when the FQ=0. The range, or
Flame Quality value for 20 mA (20mA MAP VAL), is user selectable anywhere between 40 and 100.
The factory default value is 100 (see Example 1 below). If the user selects a value of 50, when the
Flame Quality reaches 50, the analog output will be 20 mA (see Example 2 below).
If Flame SIGNAL was selected, the analog output will be 4 mA when the flame signal is 000. The
range, or Flame Signal value for 20 mA (20mA MAP VAL), is user selectable anywhere between 400
and 999. The factory default is 999. If the user selects a MAP VAL of 500, when the Flame Signal
reaches 500, the analog output will be at 20 mA.
SELECT to Exit to Previous Menu
Return to top of the Config Menu
SELECT to Exit BACK to MAIN
Return to top of the Main Status Menu