Use and Care Manual
Installation / Assembly
11
Fire Pit Owner’s Manual
LTR50001010, Rev. M
2) All sides are completely enclosed.
This method requires at least two ventilation openings at cylinder valve 
level in the side wall, equally sized, spaced at 180 degrees (3.14 rad), 
and unobstructed.
Make sure each opening has a 
total free area of not less then 
½ square inch per pound (3.2 
sq. cm/kg) of stored fuel capac-
ity and not less then a total free 
area of 10 square inches (64.5 
sq. cm).
Ventilation openings need to 
be  provided  at  oor  level  with 
a total free area of ½ inch per 
pound (3.2 sq. cm/k) of stored 
fuel capacity and not less than 
a total free area of 10 square 
inches if the ventilation open-
ings at oor  level are in  a side 
wall, make sure there are at 
least two openings. The bottom 
of the openings shall be at oor level and the upper edge no more than 
5 inches (127 mm) above the oor. The openings need to be equally 
sized, spaced at 180 degrees (3014 rad) and unobstructed.
Make sure every opening has minimum dimensions to permit the en-
trance of a 1/8 inch (3.2mm) diameter rod.
There shall be a minimum clearance of 2 inches (40.8mm) between the 
lower surface of the oor and the propane gas supply cylinder enclo-
sure and the ground.
W
ID
T
H
W
ID
T
H
DEPTH
HEIGHT
Screen vents
One side openOne side open