Technical information
The CEH
Industrial unit heater
General Information:
Calculate the heat loss of the area to be heated. It is recommended that
one of the following methods be used: ASHRAE Guide and Data Book (The
American Society of Heating, Refrigeration & Air Conditioning Engineers);
The NEMA Handbook (The National Electrical Manufacturer’s Association);
or the ACCA Manual J (The Air Conditioning Contractors of America). The
layout of the space to b
e heated must be taken into consideration to determine
the selection of the heater and air displacement. Most applications benefit
from a combination of vertically and horizontally discharged air delivery. In
buildings with large doors that are frequently opened, use a high velocity
heater with horizontal air flow across the opening, or use an infrared
heater. In smaller areas where comfort is a prime c
onsideration, more
heaters of smaller capacity are recommended. Smaller KW heaters such
as the CEH005-P are also recommended for low mounting heights to avoid
discomfort and increased noise levels. Additionally, there is better air
distribution by using a greater number of lower KW heaters.
The CEH Series
◆
30
SAFETY
Thermal Safeguard
- High temperature manual reset:
turns off heater if normal operating
temperatures are exceeded
QUALITY
• High mass, tubular element for long life
• Rugged die formed construction for durability
COMFORT
• Fan delay eliminates cold draft on startup
and disperses residual heat on shutdown
CONVENIENCE
• Wire single or three phase to suit the application
• Mounts vertically or horizontally
Product Dimensions:
14”W x 16”H x 8
1
⁄4”D
Horizontal mount:
clearance requirements
Vertical mount:
clearance requirements
Horizontal Air Flow – Position heaters to allow the air flow to “wipe”
the exposed walls without blowing directly against the wall. Spacing
between the heaters should be approximately 1.5 times the “air throw” of
the heaters (approx. air throw is 12’).
Vertical Air Flow – When vertical discharging heaters are used exclusively,
the air streams must overlap to blanket outside walls and provide good
heat dis
tribution. Vertical air flow is best used for areas with high ceilings
or bays. Vertical discharging units are to be mounted high above machinery,
assembly lines, etc. Vertical discharging units are best used when the
perimeter heat loss is adequately controlled.