13 Troubleshooting (continued)
Table 13-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
ERROR CODE DESCRIPTION CORRECTIVE ACTION
E21
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
display to reset.)
One or both of the outlet sensors has
opened or shorted.
Check the sensor and its associated wiring. Repair or
replace the sensor or wiring if damaged.
Measure the resistances of the sensors and compare
the resistances to the tables on page 71. Replace if
necessary.
E22
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
display to reset.)
The inlet sensor is open.
Check the sensor and its associated wiring. Repair or
replace the sensor or wiring if damaged.
E23
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
display to reset.)
The inlet sensor is shorted.
b01
The temperature has reached the set point
+ 10°F.
• None
b02
The main control board has received a call
for heat too quickly after the previous call for
heat has ended.
The control board will release the call for heat after 60
seconds.
The control board will release the call for heat if the
outlet temperature drops 10°F.
b04
The temperature rise across the heat
exchanger has exceeded 60°F.
Verify that the system is full of water and that all air
has been properly purged from the system.
Verify that the boiler is piped properly into the heating
system. Refer to Section 6 - Hydronic Piping
for the proper piping methods for the Cadet
boiler.
Check for 120 vac to the boiler pump motor on a call
for heat. If voltage is not present, check the wiring
back to the main control board. Replace the main
control board if necessary.
If 120 vac is present on a call for heat and the boiler
pump is not operating, replace the pump.
Verify that the boiler pump is set to the proper speed
or that the pump is the proper size. Reference
Section 6 - Hydronic Piping for boiler
pump specifications.
n03
The fan speed is being limited due to the
temperature rise across the heat exchanger
exceeding 55°F.