Installation & Service Manual
13 Troubleshooting
Table 13-1 Troubleshooting Chart - No Display
FAULT CAUSE CORRECTIVE ACTION
No Display
- No 120 vac supplied to unit. Check external line switch, fuse, or breaker.
Check wiring harness connection between display
board and main control board. Connect
harness at both points.
- Bad display board. Replace board.
- Bad main control board. Replace the main control board.
- Blown fuse. Replace fuse F3 on the main control board, see
page 69 of this manual.
No Burner
Operation
- Main control board temperature set point
satisfied.
Review temperature setting.
- Remote thermostat satisfied. Review remote thermostat setting.
- Outside air temperature above Warm
Weather Shutdown (WWSD) set point for
main control board.
Check location of outside air sensor. Check
resistance of outdoor air sensor and compare to Table
13-2B on page 71 of this manual.
- Unit locked out on fault. • Consult display for specific fault. Refer to fault
descriptions on page 73 of this manual for corrective
actions.
Unit Does
Not Modulate
Above 50%
- Flue sensor open.
Verify that the flue sensor is located in the flue outlet.
Check wiring connections at the flue sensor.
Check the resistance of the flue sensor and compare
to Table 13-2D on page 71 of this manual.