2 Maintenance schedule
5
Service technician
(see the Cadet Installation & Service Manual)
General: 
  • Reported problems
  • Inspect interior; clean and vacuum if 
 necessary
  • Clean condensate trap
 • Check for leaks (water, gas, flue, 
 condensate)
  • Verify flue and air lines in good condition 
    and sealed tight
 • Check system water pressure/system 
 piping/expansion tank
  • Check control settings
 • Check ignition and flame sense 
 electrodes (sand off any deposits; clean 
 and reposition)
  • Wiring and connections
  • Perform start-up checkout and performance 
  verification per Section 10 in the Cadet 
  Heating Boiler Installation and Service 
  Manual.
  • Flame inspection (stable, uniform)
  • Flame signal (at least 10 microamps at 
     high fire)
 • Clean the heat exchanger if flue 
   temperature is more than 54°F above 
    return water temperature.
If combustion or performance 
indicate need:
   • Clean heat exchanger
 • Remove the door and burner 
  assembly.
Owner maintenance
(see pages 6 - 8 for detailed instructions)
Daily
  • Check boiler area
 •   Check pressure/temperature 
  gauge
Monthly
  • Check vent piping
  • Check air piping
  • Check air and vent termination 
 screens
  • Check relief valve
  • Check condensate drain system
 • Check air vents
Periodically
  • Test low water cutoff (if used)
  • Reset button (low water cutoff)
Every
6 months
 • Check boiler piping (gas and 
    water) for leaks
  • Operate relief valve
End
of season 
months
 • Shut boiler down (unless boiler 
     used for domestic hot water)
 WARNING
Follow the maintenance procedures given throughout this manual. Failure to perform the service and 
maintenance or follow the directions in this manual could result in damage to the boiler or system, 
resulting in severe personal injury, death, or substantial property damage.