Viewable and changeable control parameters
Temperature Units (°C/°F) 
The control can be configured to display temperature in 
either °C or °F. This parameter can be changed by accessing 
parameter u01.
Set SH Temperature
The Space Heat Demand Temperature can be adjusted UP or 
DOWN by accessing parameter u02. Temperature range is 
32°F to parameter P90.
Set tank DHW Tank Setpoint (if tank sensor present)
The DHW Setpoint Temperature can be adjusted UP or 
DOWN by accessing parameter u03. Temperature range is 
60°F to 185°F.
Set SH Setpoint at Minimum Outdoor Temperature
When the outdoor air temperature drops to 25°F, the 
calculated set point will be at this setting (reference Table 4-3 
in the Cadet Heating Boiler Installation and Service Manual). 
If the outdoor air temperature drops further, the set point 
will continue to increase above this setting. However, if SH 
set point is set lower than the calculated set point, the water 
temperature will be limited by the SH set point instead. This 
parameter can be changed by the installer by accessing the 
P01. Temperature range is 68°F to 250°F. 
 CAUTION
Before changing parameters, note the 
settings so that the unit can be returned to 
its original operating parameters.
4 Operating information
Access modes
User
Press the ENTER button for 5 seconds.
Installer
Most parameters are available only to the installer, accessible 
by entering the installer key combination: Press the ENTER 
and DOWN buttons simultaneously for 5 seconds. 
Saving parameters (reference the Parameter Table 
in the Cadet Heating Boiler Installation and Service Manual)
To save parameters and exit programming:
Press the ENTER button to go to the end of the Parameter 
List, then press ENTER again. Otherwise, the parameters 
will be saved automatically after Timeout.
To enter a parameter and continue programming:
Press the UP or DOWN button to change parameters. Press 
ENTER to move to the next parameter and to the end of 
the Parameter List. Press ENTER to save and return to 
the Base Screen. Otherwise, the parameters will be saved 
automatically after Timeout.