Specifications
- 26 -
AS/CA S002:2010 COPYRIGHT
OCTOBER 2010
5.5.1.1.2 CE should not recognise as a ring signal an AC voltage of less than
10 V r.m.s., or a ring signal of less than 100 ms duration.
5.5.1.1.3 CE in the OFF-LINE state should withstand 2 min of continuous non-
cadence, 90 V r.m.s. ring signal at 55 Hz superimposed on 48 V d.c.
The ring signal should be applied to the terminals of the CE.
5.5.1.1.4 Under fault conditions, ring signal voltage may also be applied to
the line terminals of the CE which is in the ON-LINE condition. The CE
should remain undamaged if this should occur. A suggested test
configuration is shown in Figure 6.
5.5.1.1.5 When a ring signal of 25 Hz sine wave at 95 V r.m.s. superimposed on
56 V d.c. (with a total source impedance of 470 Ω) is applied to the
line terminals of CE as shown in Figure 7, the DC component of the
current flowing shall not exceed 600 µA.
Compliance with Clause 5.5.1.1 should be checked by using the
method described in Clause 6.7.6.
5.5.1.2 Ringer Equivalence Number (REN)
CE shall have a REN of not greater than 3.
Note 1: The method for determining REN is given in Clause 6.7.6.
Note 2: It is recommended that CE have a REN of not greater than 1 to
allow the parallel operation of other CE.
Note 3: Carrier or carriage service providers may only support a total REN
of 3.
Note 4: The total value of REN for CE operating in parallel is the sum of the
RENs of each CE.
Note 5: As CE may also be required to operate in conjunction with the
standard telephone port of a CSS, the requirements of
AS/CA S003 [4] should also be considered.
Note 6: The REN should be stated on the CE and in the user documentation
to assist customers when connecting multiple CE to a carrier
network.
Compliance with Clause 5.5.1.2 should be checked by using the
method described in Clause 6.7.6.
5.5.1.3 Meter signal detection
5.5.1.3.1 General
5.5.1.3.1.1
A meter pulse received from the PSTN will be a 12 kHz transverse
signal. The availability of this signal is subject to negotiation with the
carrier or carriage service provider concerned.
5.5.1.3.1.2 The meter signal detector is deemed to have operated when an
unambiguous output occurs on the application of an input signal.
The CE supplier should state the expected response of the CE to the
meter signal.










