Installation manual

GE Security
g
APPENDIX 3: EXPANDER NUMBERS FOR REPORTING
EXPANDER TROUBLE
The tables below list the device numbers that will be reported for each expander/keypad where a trouble
condition is present. For trouble conditions relating to the control panel, the device number is “0”.
Keypads
KEYPAD PART 1
1 192
2 200
3 208
4 216
5 224
6 232
7 240
8 248
Wireless receiver NX-448E
Wireless receiver DIP 1 DIP 2 DIP 3 Expander number reported
1 OFF OFF OFF 35
2 ON OFF OFF 36
3 OFF ON OFF 37
4 ON ON OFF 38
5 OFF OFF ON 39
6 ON OFF ON 32
7 OFF ON ON 33
8 ON ON 34 ON
Output module NX-507E or NX-508E
Output module DIP 1 DIP 2 DIP 3 Expander number reported
1 ON ON OFF 24
2 OFF OFF ON 25
3 ON 26 OFF ON
4 OFF ON ON 27
5 ON ON ON 28
6 OFF OFF OFF 29
7 ON OFF OFF 30
8 OFF ON OFF 31
NX-4-EUR Installation manual Page 89 08/09/04