Installation manual
GE Security 
g 
Segment 4 
1 =  On: enables zone activity monitor 
 2 = 
On: enables end of line resistor defeat on non-fire/non-keyswitch 
zones 
 3 = 
On : enables zone to act as request to exit input / disables for 
alarm activation 
  4 =  On : enables zone to act as access entry point (Door Shunt) (…) 
 5 = Reserved 
 6 = Reserved 
 7 = Reserved 
 8 = Reserved 
Segment 5 
1-8 Reserved 
Note : 
… 
Refer to NX-1701E card reader installer manual. Do not enable this segment 
unless configured with Access Control. 
LOCATION 112 - CONFIGURATION GROUP 2 ALARM EVENT CODE (1 segment, numerical data) 
Location 112 contains the event code that is sent for a Contact ID or SIA report. The 
desired event code should be chosen from the list on pages 121-122. The zone ID will be 
the zone that is in alarm. 
This location is not used for slow speed formats (like 4+2 and 3+1). This location may 
also contain the alarm report code for the Robofon format (value 00-99). 
LOCATION 113 - CONFIGURATION GROUP 2 CHARACTERISTIC SELECT (5 segments, feature   
selection data) 
Use the “Configuration Group Characteristic Selections” described in Location 111. 
LOCATION 114 - CONFIGURATION GROUP 3 ALARM EVENT CODE (1 segment, numerical data) 
Location 114 contains the event code that is sent for a Contact ID or SIA report. The 
desired event code should be chosen from the list on pages 121-122. The zone ID will be 
the zone that is in alarm. 
This location is not used for slow speed formats (like 4+2 and 3+1). This location may 
also contain the alarm report code for the Robofon format (value 00-99). 
LOCATION 115 - CONFIGURATION GROUP 3 CHARACTERISTIC SELECT (5 segments, feature   
selection data) 
Use the “Configuration Group Characteristic Selections” described in Location 111. 
LOCATION 116 - CONFIGURATION GROUP 4 ALARM EVENT CODE (1 segment, numerical data) 
Location 116 contains the event code that is sent for a Contact ID or SIA report. The 
desired event code should be chosen from the list on pages 121-122. The zone ID will be 
the zone that is in alarm. This location is not used for slow speed formats (like 4+2 and 
3+1). This location may also contain the alarm report code for the Robofon format (value 
00-99). 
NX-4-EUR Installation manual  Page 61   08/09/04 