Installation manual

GE Security
g
Programming the outputs
LOCATION 45 – Reserved
LOCATION 46 - AUXILIARY OUTPUT 1-2 SPECIAL TIMING (2 segments, feature selection data)
Location 46 contains special timing feature activation for the 2 auxiliary outputs. Segment
1 corresponds to output 1 and segment 2 corresponds to output 2.
Segment 1-2
1 =
On: if output should be timed in minutes; Off: if timed in
seconds
2 = On: if output should latch; Off: if output should be timed
3 =
On: if output should stop timing when the code is entered; Off:
if the output should continue to time when the code is entered
4 =
On: if output should only activate between the closing and
opening time in locations 52 and 53
5 =
On: if output should only activate between the opening and
closing time in locations 52 and 53
6 =
On: if output should be inverted (0 volts going to 12 volts when
activated)
7 = Reserved
8 = Reserved
LOCATION 47 - AUXILIARY OUTPUT 1, EVENT AND TIME (2 segments, numerical data)
Segment 1 Use the chart below to select the event that will activate auxiliary
output 1 (relay 1)
Segment 2 Program the timing from 0-255 (minutes or seconds, depending on the
data programmed in segment 1, location 46). Programming a “0”
makes the output follow the event
LOCATION 48 - AUXILIARY OUTPUT 2, EVENT AND TIME (2 segments, numerical data)
Segment 1 Use the chart below to select the event that will activate auxiliary
output 2 (relay 2)
Segment 2 Program the timing from 0-255 (minutes or seconds, depending on the
data programmed in segment 2, location 46). Programming a “0”
makes the output follow the event
LOCATION 49-50 - Reserved
NX-4-EUR Installation manual Page 50 08/09/04