NetworX™ Series NX-216E Zone Expander Module Installation and Startup
© 2005 GE Security All rights reserved. These instructions do not purport to cover all details or variations in equipment nor to provide every possible contingency to be met during installation, operation, and maintenance. If further information is desired or if particular problems arise that are not covered sufficiently for the purchaser’s purpose, the matter should be referred to GE Security.
TABLE OF CONTENTS I. GENERAL DESCRIPTION ............................................................................................................................. 4 II. ORDERING INFORMATION......................................................................................................................... 4 III. BOARD INSTALLATION ............................................................................................................................... 4 IV. WIRING .......................
GENERAL DESCRIPTION I. The NX-216E is a microprocessor-controlled 16-zone expander for the NetworX control panels (refer to Compatibility chart on the back of this manual). Up to five NX-216E zone expander modules can be added to the NX-8 or NX-8-CF control panels with a maximum zone count of 48 zones. Up to twenty-three expanders can be added to the NX-8E and NX-8E-CF controls with a maximum zone count of 192 zones.
WIRING IV. Any unused zones must have the EOL resistor across it (unless all eight are disabled by dip switch 6). Figure IV—1 TERMINAL DESCRIPTION V. POS COM DATA TAM AUX Z9 COM Z10 Z11—Z24 Connect to the KP POS terminal of the NetworX control panel (refer to Compatibility chart on the back of this manual). Current draw is 30 mA. Connect to the KP COM terminal of the control panel. Connect to the KP DATA terminal of the control panel.
VI. DIP SWITCH SETTINGS (6 position) The first thing that must be decided is the starting zone of this particular zone expander. The starting zone must be on a boundary of eight (8) zones. The sixteen (16) zones for this module will move out from this starting position. To set the starting zone, set the dip switch according to the table below: THE POSITION OF ALL SWITCHES IS ONLY UPDATED WHEN THE NX-216E IS POWERED UP. BEFORE YOU CHANGE THE POSITION OF THESE SWITCHES YOU MUST POWER DOWN THE EXPANDER.
VII. ENROLLING THE EXPANDER The NetworX control panels have the ability to automatically find and store in memory the presence of all keypads, zone expanders, wireless receivers and any other module connected to the data terminal. (Refer to Compatibility chart on the back of this manual). This allows these modules to be supervised by the control panel. To enroll the modules enter the Program Mode of the control panel (refer to the installation manual for the specific control panel).
DATA 14 15 16 17 18 19 20 DESCRIPTION OF DEFAULT CONFIGURATION ENTRY/EXIT DELAY 1 WITH GROUP BYPASS ENABLED - A trip will start entry delay 1. This zone will bypass when the "Group Bypass" command is entered at the keypad. The lack of a trip during exit delay will enable the Automatic Bypass or Instant mode if so programmed. INTERIOR FOLLOWER WITH GROUP BYPASS ENABLED - This zone will be instant when the system is armed and no entry or exit delays are being timed.
IX. ZONE CONFIGURATION AND PARTITION The programming for all zone information is performed in the NetworX control panels (refer to Compatibility chart on the back of this manual). For instructions on accessing and programming the control panel as well as changing the characteristics of a configuration group, refer to the installation manual for the corresponding control panel. The following programming information is taken from the NX-8 Installation Manual.
X.
LOC 35 36 DESCRIPTION ZONES 41 – 48 CONFIGURATION GROUP ZONES 41 – 48 PARTITION SELECT Segment 1 2 3 Zone 41 42 43 1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 DEFAULT 6-6-6-6-6-6-6-6 4 44 1 2 3 4 5 6 7 8 5 45 1 2 3 4 5 6 7 8 DATA 6 46 1 2 3 4 5 6 7 8 7 47 1 2 3 4 5 6 7 8 8 48 1 2 3 4 5 6 7 8 NOTE: THE FOLLOWING LOCATIONS ARE ONLY AVAILABLE ON THE NX8-E and NX-8E-CF PANELS 170 171 172 173 174 175 ZONES 49 – 56 CONFIGURATION GROUP ZONES 49 – 56 PARTITION SELECT Segment 1 2 3 Zone 49 50 51 1 1 1
LOC 176 177 178 179 180 181 182 183 12 DESCRIPTION ZONES 73 – 80 CONFIGURATION GROUP ZONES 73 – 80 PARTITION SELECT Segment 1 2 3 Zone 73 74 75 1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 ZONES 81 – 88 CONFIGURATION GROUP ZONES 81 – 88 PARTITION SELECT Segment 1 2 3 Zone 81 82 83 1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 ZONES 89 – 96 CONFIGURATION GROUP ZONES 89 – 96 PARTITION SELECT Segment 1 2 3 Zone 89 90 91 1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 ZONES 97 – 104 CONFIGURATION GROU
LOC 184 185 186 187 188 189 190 191 DESCRIPTION ZONES 105 – 112 CONFIGURATION GROUP ZONES 105 – 112 PARTITION SELECT Segment 1 2 3 Zone 105 106 107 1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 ZONES 113 – 120 CONFIGURATION GROUP ZONES 113 – 120 PARTITION SELECT Segment 1 2 3 Zone 113 114 115 1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 ZONES 121 – 128 CONFIGURATION GROUP ZONES 121 – 128 PARTITION SELECT Segment 1 2 3 Zone 121 122 123 1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 ZONES 129 – 136
LOC 192 193 194 195 196 197 198 199 14 DESCRIPTION ZONES 137 – 144 CONFIGURATION GROUP ZONES 137 – 144 PARTITION SELECT Segment 1 2 3 Zone 137 138 139 1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 ZONES 145 – 152 CONFIGURATION GROUP ZONES 145 – 152 PARTITION SELECT Segment 1 2 3 Zone 145 146 147 1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 ZONES 153 – 160 CONFIGURATION GROUP ZONES 153 – 160 PARTITION SELECT Segment 1 2 3 Zone 153 154 155 1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 ZONES 161 –
LOC 200 201 202 203 204 205 DESCRIPTION ZONES 169 – 176 CONFIGURATION GROUP ZONES 169 – 176 PARTITION SELECT Segment 1 2 3 Zone 169 170 171 1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 ZONES 177 – 184 CONFIGURATION GROUP ZONES 177 – 184 PARTITION SELECT Segment 1 2 3 Zone 177 178 179 1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 ZONES 185 – 192 CONFIGURATION GROUP ZONES 185 – 192 PARTITION SELECT Segment 1 2 3 Zone 185 186 187 1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 NX-216E Zone Expander D
XI. SPECIFICATIONS OPERATING POWER 12VDC Supplied from NetworX control panel or NX-320E AUXILIARY POWER Supplied from NetworX control or NX-320E Current limited to 100mA CURRENT DRAW 30mA LOOP RESISTANCE 300 Ohms Maximum LOOP RESPONSE Selectable 50mS or 500mS OPERATING TEMPERATURE 32 to 120 degrees F DIMENSIONS 6.0" Wide 2.125" High 1.0" Deep SHIPPING WEIGHT 2 lbs.