Operating instructions
79
User Interface Display
Explanation
CH Settings
4. Central Heating (CH) modes available:
•  CH Mode = 0 ‘CH with Thermostat’
•  Boiler will attempt to satisfy CH demand while CH 
thermostat input is closed.
•  Boiler will modulate its ring rate to maintain CH set 
point and match system heat load.
•  CH set point adjusted in ‘Settings’ submenu under ‘User 
Menu’ 
•  CH Mode = 1 ‘CH with Thermostat and Outdoor Reset’
•  Boiler will attempt to satisfy CH demand when CH 
thermostat input is closed.
•  Boiler will modulate its ring rate to maintain CH set 
point and match system heat load.
•  CH set point calculated as function of outdoor 
temperature using outdoor reset curve. See gure A-2
• CH Mode = 2 ‘CH with Full Outdoor Reset’
•  Boiler will permanently attempt to satisfy CH 
demand.
•  CH thermostat input is ignored.
•  CH set point calculated as function of outdoor 
temperature using outdoor reset curve. See gure A-2
•  CH Mode = 3 ‘CH with Permanent Demand’
•  Boiler will permanently attempt to satisfy CH 
demand.
•  CH thermostat input is ignored.
•  CH set point is adjusted in ‘Settings’ submenu under 
‘User Menu’
Note:
• Once CH demand is satised (i.e. CH thermostat opens or 
boiler determines its minimum ring rate exceeds system 
heating load):
• Burner shuts off, boiler enters post purge.
• CH pump continues to run for 30 seconds.
• Control will wait until Anti-cycle time of 180 seconds 
elapses before boiler res again. Prevents short- 
cycling.
•  The internal heat exchanger pump is energized anytime demand 
exists regardless of Pump Mode setting or type of demand (CH or 
DHW).
APPENDIX A - CONTROL MODULE