User Interface Display
Explanation
Boiler Status
Boiler stores information regarding total CH and DHW run time 
in hours. 
Data stored in non-volatile memory and retained in event of 
power failure.
Boiler logs last 16 blocking errors and 16 lockout errors in 
non-volatile memory. Information retained in event of power 
failure.
Most recent blocking error code and its text description 
displayed with elapsed time in hours since logged.
Optional Computer interface Kit purchased separately to view 
extended error code history
Boiler Conguration
‘Address Selection” screen used to set boiler position in multiple 
boiler cascade installation. Refer to Multiple Boiler Installation 
Manual.
Default setting of ‘0’ indicates boiler is operating in single boiler 
mode.
Boiler incorporates integrated Low Water Cutoff device (LWCO) 
that disables boiler when low water condition exists. LWCO 
device located at high point of internal Heat Exchanger loop to 
detect low water condition.
Detection of low water condition will result in blocking error; 
boiler will automatically resume normal operation when proper 
water level returns. Refer to Troubleshooting Guide.
LWCO device can be disabled for diagnostic purposes or where 
applicable code permits.