1.4 Sequence of Operation
Operational State User Interface Display Explanation
If ame detected before Gas Valve 
opens during ignition boiler will 
lockout.
Please refer to troubleshooting 
guide.
Gas Valve energized to deliver air/
fuel to burner.
If ame undetected after 3 sec-
onds boiler will de-energize Gas 
Valve and enter post purge mode 
for 30 seconds.
Ignition attempted 5 times before 
lockout.
Boiler will run provided all op-
erational and safety devices are 
within limits
Refer to for more information.
Control module adjusts ring rate 
according to heating demand. 
When Boiler detects demand met, 
will enter post purge mode then 
standby mode.
If simultaneous demand for 
Central Heat and DHW, boiler will 
enter DHW Priority Mode.
Priority mode limits amount of 
time boiler can run in DHW mode 
to meet CH demand.
Max DHW Priority Time setting 
determines maximum time 
allowed for DHW heating mode.
Please refer to section Appendix A 
section 1.5 for more information.
Flame
Detected?
Gas Valve
Energized
Flame 
Detected?
Heat Demand
Met?
DHW 
Priority 
Mode
Simultaneous 
DHW + CH
Demand?
No
Yes
No
Yes
See Max DHW 
Priority Time 
Setting
No
After 2 seconds
After 3 seconds
No
30 second 
post purge
Yes
Yes
Lockout 
Error A21
Note:
5 Ignition 
trials, 
then 
Lockout A01
APPENDIX A - CONTROL MODULE