Operating instructions
60
Is harness plugged into Supply 
Water Sensor?
Is harness plugged into Control 
Module J5?
_ P _ _ _
Blocking Error E 5 1 
Supply Sens Open
Insert Harness
Replace Supply 
Water Sensor
Disconnect J5 from Control 
Module. Using digital meter 
measure check continuity of 
white wires between Control 
and Sensor. Continuity?
Using digital meter measure 
resistance between Supply 
Water Sensor terminals J5-11 
and J5-3. Measure resistance 
of Sensor with digital meter. 
Estimate Sensor temperature.  
Does it fall in the range of the 
Resistance Chart?
Replace Wires
50 to 9010 to 32
9K to 24K ohms
150 to 200
90 to 130
°F
°C
Resistance
130 to 150
2K to 1K ohms
2K to 3K ohms
3K to 9K ohms
54 to 66
32 to 54
66 to 94
Supply Water Sensor
Resistance Chart
Disconnect field wiring. Is 
continuity between field wiring 
neutral and ground less than 
10 ohms?
Is field grounding conductor 
connected to High Voltage 
Terminal Strip 120 VAC (G)?
NO
YES
_ P _ _ _
Blocking Error E 4 6 
Faulty ground
Connect ground 
conductor
YES
NO
Correct faulty ground 
conductor
Replace Control 
Module
NO
YES
YES
NO
YES
NO
Replace Control 
Module
13 - TROUBLE SHOOTING