Operating instructions
49
Screen Display Explanation
Go to Page For 
Troubleshooting 
Low water cutoff sees no water. Go to Page 56
Flue temperature sensor sees temperature 
higher than 200°F.
Go to Page 57
Return water temperature sensor sees 
temperature higher than 200°F.
Go to Page 58
Control board internal error. Power down then 
power up boiler. If error repeatedly occurs 
replace control module.
Replace Control 
Module
Boiler is powered by three wires, hot, neutral 
and ground. E44 displays when neutral wire is 
not neutral.
Go to Page 58
Control board sees power supply frequency not 
in range of 59 to 61 Hz.
Go to Page 59
Boiler power supply ground wire is not 
grounded.
Go to Page 60
Control board internal error. Power down then 
power up boiler. If error repeatedly occurs 
replace control module.
Replace Control 
Module
Supply temperature sensor is open. No 
continuity.
Go to Page 60
Return water temperature sensor is open. No 
continuity.
Go to Page 61
Flue temperature sensor is open. No 
continuity.
Go to Page 62
Supply water temperature sensor is shorted. 
'0' Ohm
Go to Page 62
Return water temperature sensor is shorted. 
'0' Ohm
Go to Page 63
Flue temperature sensor is shorted. '0' Ohm Go to Page 63
Reset button was pressed too many times.
Error Clears in 1-2 
minutes
Fault detected in blower motor system. Go to page 59
3
Blocking Error
Flue Gas Error
E 
39
13 - TROUBLE SHOOTING