Operating instructions
38
9.4 Boiler Start-up and Operational Test
1. 
Verify air is purged from hydronic piping
2.  System test pumps - verify each pump is 
operational
3.  Verify gas piping
• 
Conrm pressure test. See section 7.3.
• 
Visually inspect piping to determine there are no 
open ttings or ends, and all valves at unused 
outlets are closed and plugged/capped.
• 
Purge air from piping
• 
Check piping and connections for leaks 
immediately after gas is turned on. Shut off 
gas supply and make necessary repairs if leaks 
found.
4.  Follow OPERATING INSTRUCTIONS to initiate boiler 
operation. See section 10.
5.  Inspect combustion air and vent piping. Verify pipe 
is not leaking and terminations are unobstructed 
and vent gas discharge is not a nuisance or hazard.
6.  Verify boiler functions.
7.  Inspect condensate disposal system. Verify 
condensate ows adequately and is disposed 
properly.
8.  Check control module operation.
9.  Check eld sourced limits, low water cutoffs, etc. 
per manufacturer's instructions.
9.5 Check Combustion 
Natural Gas
1.  Measure input. English units*
• 
Turn off gas to all other appliances.
• 
Activate some heating zones to dissipate heat.
• 
Set boiler on high re.
• 
Use ½, 1 or 2 cu ft dial on gas meter. Measure 
time required for one or more complete 
revolutions. Measure time for 1-2 minutes.
• 
Calculate input.
Input (MBH) =
3600 x cu ft
 seconds
Example: Gas ow from
  Meter = 2 cu ft 
  Measured time = 72 seconds
 Rate (MBH) =
3600 x 2 cu ft
= 100 MBH
 72 seconds
*Metric - See Glossary 
2.  Compare measured input to table. Adjust input rate 
if needed using Table 12 below.
Table 12 - Rate @ High Fire
Rate @ High Fire
Size From To
050 45 51
075 65 76
100 90 102
150 140 153
200 185 204
299 285 315
Natural Gas and Propane
3.  Measure CO
2
 at high re and compare to table. 
Adjust CO
2
 if needed using gure 9-3 & 9-4. See 
gures 9-5 and 9-6 for combustion air analyzer 
port. 
9 - START UP PROCEDURE