Operating instructions
36
9.1 Fill Boiler With Water And Purge Air
NOTICE
To maintain boiler efciency and prevent boiling 
inside the heat exchanger, ush entire heating 
system until clean. 
• Flush heating system, including all heating zones.
• Fill boiler with potable water.
• 
Fill boiler and system piping with water (or 
antifreeze-water solution, if used). See antifreeze 
information page 13. Purge air from boiler using air 
vent. Purge air from system piping.
• 
Inspect system piping and boiler connections. Repair 
any leaks immediately.
• 
Activate all heating zones and calls for heat, 
including CH calls and DHW calls (if available).
• 
Close manual gas shut off valve. Let system run for 
30 minutes. When boiler goes into lockout, reset 
boiler by pressing "Reset" button until boiler resets.
• 
Do not open gas shutoff valve until all air is purged 
from system.
9.2 Fill Condensate Trap with Water
• 
Disconnect spring tension clip from condensate hose 
barb. See gure 9-1.
• 
Disconnect tubing below from hose barb. 
• 
Pour approximately 2 cups (473 ml) of water into 
condensate drain.
• 
Reconnect tubing to hose barb with spring tension 
clip. See gure 9-1.
FIGURE 9-1 Condensate Drain Assembly
NOTICE
IMPORTANT: Condensate trap must be manually 
lled with water at initial start up.
2. Reconnect hose to hose   
barb with spring tension clip 
 before starting boiler.
1. Disconnect spring tension 
clip from hose barb and ll 
Condensate trap with water.
9 - START UP PROCEDURE