Operating instructions
30
6.8 Multiple Boiler Venting Installation
•  Multiple boiler application boiler can vent individually 
or use common vent pipes.
•  If boilers vent individually follow guidelines as 
described in gures 6-1 through 6-7.
•  If boilers vent through common vent pipes, as shown 
in Figure 6-17, choose common vent pipe per Table 8.  
Choose size from Table 9 for pipes between boiler and 
common vent pipes. 
•  Longest individual vent lengths and common vent 
length together must be shorter than 100 ft. (30m). 
H + L ≤ 100 ft (30m) (See gure 6-17)
•  Each boiler must have ow check valve to prevent ue 
gas back ow. 
•  External terminals follow same rule as single boiler 
venting as described in Section 6.6 and 6.7
FIGURE 6-17 Mulitple Boilers With Common Venting Pipe
Model
Minimum 
Diameter
050 2" (51mm)
075 3" (73mm)
100 3" (73mm)
150 3" (73mm)
200 3" (73mm)
299 3" (73mm)
Table 8 - Minimum Diameter for Individual 
Boiler in Common Venting System
Total 
Firing 
Rate
Minimum 
Diameter of 
Common vent 
pipes if 
L< 50 ft (16m)
Minimum 
Diameter of 
Common vent 
pipes if 
L>50 ft (16m)
400 4" (101mm)
5" (127mm)
600
5" (127mm)
6" (152mm)
800
1000
6" (152mm)
7" (177mm)
1200
1400
1600
7" (177mm)
8" (203mm)
1800
2000
Table 9 - Common Venting Pipe Diameters
6 - COMBUSTION AIR AND VENT PIPING
L
H
Flow Check 
Valve
Flow Check 
Valve
Flow Check 
Valve
12" (305mm)
Anticipated 
Snow Line
Vent
Combustion 
Air
Ground Level