Operating instructions
29
Multiple 
Family 
Dwellings
Vent shall not terminate directly above 
paved sidewalk or paved driveway located 
between two single-family dwellings serving 
both dwellings.
7' (2.1m) 
Minimum
3' (0.9m) 
Minimum
Termination
Stones, 
Balls, Etc.
Position combustion air and vent 
termination where it will NOT be damaged by 
foreign objects, such as stones, balls, etc.
People or 
Pets
Locate combustion air and vent termination to 
prevent accidental contact with people or pets.
Eddy, Flue 
Gases
Position termination so it will not be 
effected by wind eddy, air born leaves, 
snow, or recirculated vent gases. Give 
consideration to excessive wind and locate 
away from windward side of building.
Vapors
Position termination where vent vapors are 
not objectionable.
Walkways
Locate vent termination minimum 7' 
(2.1m) above any public walkway,  with 
consideration to condensate.
Meters, 
Regulators, 
deck, porch
Vent termination US only - 4’ (1.2m), 
Canada - 6' (1.9m) horizontally from, 
no case above or below, electric meters, 
gas meters, regulators, and relief 
equipment, or under deck or porch.
Vegetation, 
Plants & 
Shrubs
Keep vent termination 3’ minimum 
(0.9m) away from vegetation. Position 
termination where vent vapors will not 
damage plants/shrubs or air conditioning 
equipment.
FIGURE 6-15 
FIGURE 6-16 
6 - COMBUSTION AIR AND VENT PIPING