IMPORTANT: Do not use a tankless coil if water is excessively hard with lime or other deposits which will accumulate inside coil.
A. Mounting Aquastat Control
The control configuration on this boiler has been set up so that the Honeywell L8124C Combination Hi/Low Limit Aquastat Relay mounts on the
tankless coil. This maximizes tankless coil performance by making the burner respond more quickly to a call for domestic hot water.
The boiler is completely wired according to schematic wiring diagram. (See Fig. 14.) The installer must mount the L8124C Aquastat on control
well in 3/4-in. tapping on tankless coil. (See Fig. 7.)
B. Tankless Coil Piping
Piping is as shown in Fig. 8. A tempering valve (mixing valve) is recommended. A flow restrictor may be required on tankless coil inlet piping
so that flow rates are matched to boiler heat input. See Table 3.
PROCEDURE 4INSTALLATION SYSTEM PIPING
1. Place boiler in selected location as close to flue as possible. (See Fig. 4.) Boiler is shipped assembled. Only the factory-supplied relief valve
needs be installed.
Fig. 5Air Openings for Closet of Utility Room Installations
A95594
VENTILATING
GRILLE
COMBUSTION
AIR GRILLE
Fig. 6Fresh Air Duct for Tightly Sealed House
A95595
BOILER
FRESH AIR
DUCT
Table 2Fresh Air Duct Capacities for Ducts Supplying Fresh Air to Boiler in Tightly Constructed Houses (Btuh)*
FRESH AIR DUCT SIZE (IN.) 1/4IN. MESH SCREEN WOOD LOUVERS METAL LOUVERS
3-1/2 X 12 144,000 36,000 108,000
8X8 256,000 64,000 192,000
8X12 384,000 96,000 288,000
8X16 512,000 128,000 384,000
*Based on opening covered by 1/4-in. mesh screen, wood louvers, or metal louvers.
8