1. 
Do not install copper supply and return piping directly 
into aluminum boiler section castings due to galvanic 
corrosion between dissimilar metals. 
2. 
Use iron, steel bushings or pipe connectors between 
copper system piping and boiler to make fi nal 
connection to boiler. 
3. 
Use of dielectric unions is acceptable, installer supplied.
4. 
Packaged boiler is furnished with iron piping in front 
boiler section for supply and return connections.
5. 
Install all of radiation units (panels, radiators, 
baseboard, or tubing) and supply and return mains 
fi rst, when installation of boiler is for new heating 
system. 
6. 
After installation of all heating system piping and 
components; make fi nal connection of system piping to 
boiler.
7. 
Hot water boiler installed above radiation level or 
as required by authority having jurisdiction must be 
equipped with low water cut off device (included with 
boiler). 
8. 
Periodic inspection is necessary, as is fl ushing of fl oat 
type devices, per low water cut off manufacturers 
specifi c instructions.
Expansion Tank And Make-Up Water
• Determine required system fi ll pressure, design 
temperature, and water content. 
• Boiler contains 3.0 gallons (U.S.). Size expansion tank 
accordingly. Consult expansion tank manufacturer for 
proper sizing information. 
• Connect properly sized expansion tank (not furnished) 
See Figure 2, for diaphragm type expansion tank. 
For diaphragm type expansion tanks, adjust tank air 
pressure to match system fi ll pressure. 
• Install air vent (furnished) as shown for diaphragm type 
expansion tank system only. 
• Install make-up water connections as shown and per 
local codes. 
• If pressure reducing valve is used, adjust to match 
system fi ll pressure. Verify clean water supply is 
available when connecting cold make-up water supply 
to boiler. When water supply is from well or pump, 
install sand strainer at pump.
4 - NEAR BOILER PIPING
Figure 2  - Diaphragm Type Expansion Tank 
Piping
Figure 3  - Relief Valve Discharge Piping
 WARNING
Burn and scald hazard. Safety relief valve could    
discharge steam or hot water during operation. 
Install discharge piping per these instructions.
! 
Check local codes 
for maximum 
distance from 
fl oor or other 
allowable safe 
point of discharge
RELIEF VALVE
DISCHARGE 
PIPING