The successful use of the CSC-ENVM card in the AGS+ chassis requires that the chassis be installed
and maintained to preclude unintended shutdowns.
The AGS+ chassis has an internal blower fan that pulls air through the card cage from left to right
(with the chassis front toward you). If either the intake or exhaust vents are blocked in any way, this
air-cooling function will be impaired and the CSC-ENVM, sensing this, will shut the chassis down.
If the temperature of the air being drawn into the chassis is already higher than desirable, the air
temperature inside the chassis may be too high. This condition can occur when the wiring closet or
rack in which the chassis is mounted is not ventilated properly, when the exhaust of one chassis (or
other electronic device) is placed so it enters the air intake vent of the chassis, or when the chassis
is the top unit in an unventilated rack. With any of these conditions, a shutdown by the CSC-ENVM
can be induced.
The chassis is designed to operate in a level, dry, clean, well-ventilated, and air-conditioned
environment. While chassis shutdown due to a fault or failure is one of the designed purposes of the
CSC-ENVM, unnecessary shutdowns due to air intake blockage and poor external ventilation can
and should be avoided.
Note The AGS+ can be installed in wiring closets and rack systems as long as the above
prerequisites are observed before installation and are maintained throughout chassis operation.
AGS+ Site Environment
The AGS+ chassis can be used as a tabletop or rack-mounted system in a data processing or lab
environment. Because the large cooling fan in the AGS+ chassis is somewhat noisy (approximately
60 decibels), the chassis is designed for unattended or computer room use.
General site requirements for the AGS+ chassis are as follows:
• Operating temperature range: 32 to 104 F (0 to 40 C)
• Operating humidity range: 5 to 95%, noncondensing
• Air flow: Depending upon the temperature and cooling capability of your site, the chassis will
require a minimum amount of clearance on all sides to prevent the chassis from taking in the
exhaust (heated) air of other equipment.