User guide

30
12.5 Report A5 – Raceway Connection Warnings
This report identifies nodes that share the connections of trays (not conduits) that have different
service levels. The service level is shown after the ‘\’ next to the tray tag. In addition, it will indicate
when the node type has an inconsistent amount of connected trays. Node types are indicated in the
suffix of the node. Tray node types are E= End, T= Tee and X=Cross
12.6 Report A6 – Parallel Raceways Not Size Locked
When raceways have common from and to nodes, CableMatic will route in the first raceway (in
alphanumeric order) that will not be overloaded. If the raceway is not ‘Size Locked’, then CableMatic
assumes that it will not be overloaded. Therefore, some of the raceways will not be used if it was
preceded alphanumerically by a raceway that is not ‘Size Locked’. You might want to consider
having only the highest alphanumeric raceway as not ‘Size Locked.’