Specifications
PV PHOTOVOLTAIC CABLE
P H O N E : ( 8 0 0 ) 3 4 3 2 5 7 9 • F A X : ( 8 2 8 ) 3 8 9 3 9 2 2 • W W W . A D C A B L E . C O M
6
Cable Identification
Description
ADC’s Solarlink brand Photovoltaic cable has a chemically
cross-linked polyethylene insulation.
Applications
Appropriate for use in solar power applicatioins that require
2,000 volt rating. For use in grounded interconnection and
ungrounded Photovoltaic power systems.
Construction
Conductors: Stranded bare copper conductor per ASTM B-3, B-8.
Available in 7 or 19 stranded versions as well as tinned copper.
Insulation: Chemically Cross-linked polyethylene
Colors: Black, Green, White, Red. Print on one side with a
contrasting ink. An extruded stripe and other colors are avail
-
able upon request.
Industry Listings & Standards
UL Listed as Photovoltaic Cable per Standard Subject 4703 and 44
-40°C/90°C Wet and Dry Rated
Gasoline and Oil Resistant II
RoHS Compliant
Sunlight Resistant
VW-1 Flame Rating Optional
Cable Data
Part Number AWG Strand
Insulation Thick-
ness
(mils)
Nominal O.D.
(inch)
Approximate
Net Weight
lbs/1M’
3182NPV 18 7 75 .198 22.81
3162NPV 16 7 75 .208 26.80
3142NPV 14 7 75 .223 33.73
3122NPV 12 7 75 .242 43.84
3102NPV 10 7 75 .266 59.09
3082NPV 8 7 85 .316 88.12
3062NPV 6 7 85 .354 124.06
3042NPV 4 7 85 .402 179.76
3032NPV 3 7 85 .430 217.86
3022NPV 2 7 85 .462 265.39
3012NPV 1 19 105 .542 344.62
30102NPV 1/0 19 105 .583 420.75
30202NPV 2/0 19 105 .629 514.86
30302NPV 3/0 19 105 .680 631.97
30402NPV 4/0 19 105 .738 778.47
302502NPV 250 MCM 37 120 .815 943.00
303002NPV 300 MCM 37 120 .870 1113.00
303502NPV 350 MCM 37 120 .921 1284.00
304002NPV 400 MCM 37 120 .968 1453.00
305002NPV 500 MCM 37 120 1.053 1793.00
306002NPV 600 MCM 61 135 1.163 2146.00
307502NPV 750 MCM 61 135 1.268 2640.00
“ADVANCED DIGITAL CABLE INC. XX AWG (UL)
PV WIRE OR RHW-2 2000V OR USE-2 600V 90°C
WET OR DRY (-40C) SR GRII DIRECT BURIAL RoHS
E324841”
2kV Rated PV
Cross-Linked Polyethylene Insulated
18 - 750 MCM • 2000 Volts • -40°C to 90°C Wet and Dry
The information contained on this specification is intended to be used a guide in product selection and is believed to be reliable.
ADC has made every effort to ensure the data shown above is accurate at the time of publication. This specification is subject to change anytime without notice. REV0216
Bare Copper
XLPE Insulation