Specifications

App1-8 Appendix 1 PLC2Way
5. Set the parameters for the PLC to be connected at the MJ port.
[Baud Rate] (4800, 9600, 19200, 38400, 57600, 115k, bps)
Select the communication speed with the PLC connected at the MJ port.
[Parity] (None/Odd/Even)
Select the parity setting for communications with the PLC connected at the MJ port.
[Data Length] (7-bit/8-bit)
Select the data length for communications with the PLC connected at the MJ port.
[Stop Bit] (1-bit/2-bit)
Select the stop bit setting for communications with the PLC connected at the MJ port.
[Signal Level] (RS-232C/RS-485)
Select the signal level for communications with the PLC connected at the MJ port.
[Retrials]
Set the number of retrials to be attempted in the case that a communication error occurs.
[Time-Out Time] (×100 msec)
Select the receive time of the response from the PLC connected at the MJ port. If no response
is received within the specified time, a retrial is attempted.
[Send Delay Time] (× msec)
Set a time delay in sending the response to the PLC after receipt of data from the PLC
connected at the MJ port.
[Return Time] (×10 sec)
When the PLC in the PLC2Way communication is turned off, data read from the PLC is
temporarily prohibited. An inquiry for restoration is sent each time the specified return time
has elapsed.
The following options may be set depending on the PLC model.
- MITSUBISHI: A series Link
[Trans. Mode] (Trans. Mode 1/Trans. Mode 4)
Trans. Mode 1: Without CR/LF
Trans. Mode 4: With CR/LF
- OMRON: SYSMAC C, SYSMAC CV, SYSMAC CS1
[Trans. Mode] (Trans. Mode 1/Trans. Mode 2)
Trans. Mode 1: Standard (BCD without signs)
Trans. Mode 2: Special BCD (BCD with sign)
- YOKOGAWA: FA-M3, FA-M3R
[Trans. Mode] (with sum check/without sum check)
6. To reset the setting, click the [Default] button, or set the desired value.