Specifications

6. Basic Instructions
© DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
6-11
S
S10
SET S12
X0
Y10
S
S12
SET S14
X1
Y11
When step point S10 and S12 transition simultaneously (S10OFF, S12ON, there is a delay for one
scan time), and the output Y10 and Y11 will not be ON simultaneously.
S10
Y10
X00
S12
Y11
X01
STL S10
Update Input/Output
Execute
Program
Execute
Program
Execute
Program
Execute
Program
Circuit Inactivate
Step Point Transition
Commands SET Sn and Out Sn are for activating another step point. There are different occasions when these commands are used. Please see
the following examples.
SET Sn
The step ladder control that begins with S0 to S9 will move
to the next step point, the action of the previous step point
will be deleted.
S
S10
SET S12
X0
Y10
S
S12
SET S14
X1
Y11
When SET S12 executes, step
point will move from S11 to S12.
S11 and the output of (Y10) will
be deleted.