Specifications

4. Installation and Wiring
© DELTA ELECTRONCIS, INC. ALL RIGHTS RESERVED
4-14
4.4. Wiring Guidelines
Power Input Wiring
The following diagram shows various possible external power connections for DVP PLC. When wiring AC power, the ‘Live’
cable should be connected to the ‘ L’ terminal and the ‘ Neutral’ cable should be connected to the ‘ N’ terminal. When wiring DC
power, the ‘ positive’ cable should be connected to the ‘ +’ terminal and the negative should be connected to the ‘- terminal. At
no time should the power supply terminals be connected to any other terminal on the PLC.
AC Input Type
S/S X0 X1 X2
24G
NL
DC/DC
2.0A
5V
100~240VAC
The +24V supply output is rated at 0.4 Amperes. DO NOT connect external power supply to this
terminal.
FUSE Protection: there are internal fuses on all DVP PLCs. However, the fuse does not
guarantee the prevention of DVP PLC damage, but it will provide added protection.