Specifications
4. Installation and Wiring
© DELTA ELECTRONCIS, INC. ALL RIGHTS RESERVED
4-13
below 6.8
below 6.8
To suit M3.5 screw terminals
1. Cables terminating at a screw terminal of a DVP product
should be fitted with insulated crimp terminals, see examples
shown at left. Terminal screws should be tightened to
between 5 and 8 kg- cmΰ4.3 and 6.9 in- lbsα. Screw terminals
must be secure enough to prevent a loose connection from
causing a malfunction.
2. DO NOT wire to the No function terminals.
3. Input and output signal wires should not run through the same
multi-wire cable, conduit, or near high voltage cables.
4. All low voltage wires should cross high voltage cables at 90̓
when possible.
5. Use Copper Conductors only
6. 75к only
Recommended Grounding
For grounding, use at least 2mm
2
ΰAWG14αcable. Ground resistance must be less than 100ohmΰClass 3α. The PLC’s
ground should not be shared with that of the power circuits. While grounding is recommended, if it is not possible, the PLC
will still operate correctly without it. Ground terminal : All ground terminals should be linked with 2mm
2
ΰAWG14αcable. The
linked terminals should all be connected to a single earth point.