Specifications

4. Installation and Wiring
© DELTA ELECTRONCIS, INC. ALL RIGHTS RESERVED
4-10
4.3. PLC Mounting Arrangements and Wiring Notes
The installation of the DVP products has been designed to be safe and easy. Whether the products associated with this manual
are used as a system or individually, they must be installed in a suitable enclosure. The enclosure should be selected and
installed in accordance to the local and national standards.
PLC mounting arrangements
PLC should be mounted on a vertical position. To prevent a rise in
temperature, units should always be mounted on the back wall of an
enclosure. Never mount PLC to the floor or ceiling of the enclosure.
Caution:
1. Do not install units in areas with excessive or conductive dust,
corrosive or flammable gas, moisture or rain, excessive heat,
regular impact shocks or excessive vibration.
2. Do not allow debris to fall inside the unit during installation, e.g.
cut wires, shavings etc. After installation, remove the protective
paper band to prevent overheating.
3. Always ensure that units are kept as far as possible from
high-voltage cables and equipment.
DVP MPU
50mm
RURYHU
50mmRURYHU
50mmRURYHU
50mm
RURYHU
Ϩʳ DIN Rail Installation
The DVP-PLC can be secured to a cabinet by using DIN rail. The DIN rail should be 35mm high, with a depth of 7.5mm.
When mounting the PLC on a DIN rail, please use end brackets to stop any side-to-side motion of the PLC. This will reduce
the chance of any wires being pulled loose.
On the bottom of the PLC is a small retaining clip. To secure the PLC to a DIN rail, place it onto the rail and gently push up on
the clip. To remove the PLC, pull down on the retaining clip and gently pull the PLC away from the DIN rail.