Specifications

8. EX MPU and I/O Extension Units
© DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-10
Input / Output points numbering order
No matter how many points the MPU has, the input of the first I/O extension unit will start from X20 and the output will start
from Y20.
DVP14ES00R2 DVP24XP01R DVP16XM01N DVP08XN11R DVP08XP11R
8 / 6 16 / 8 16 / 0 0 / 8 4 / 4
Models Input Points Output Points
Input
Numbering
Output
Numbering
DVP14ES00R2 8 6 X00~X07 Y0~Y5
DVP24XP01R 16 8 X20~X37 Y20~Y27
DVP16XM01N 16 0 X40~X57
Ϋ
DVP08XN01R 0 8
Ϋ
Y30~Y37
DVP08XP11R 4 4 X60~X63 Y40~Y43
When MPU (DVP60ES00R) connects to a extension unit (DVP24XP01R), the input of the extension unit will start from X50
and the output will start from Y40.
Models Input Points Output Points
Input
Numbering
Output
Numbering
DVP60ES00R2 36 24 X00~X43 Y0~Y27
DVP24XP01R 16 8 X50~X67 Y30~Y37