Specifications

2. Standard Specifications
© DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 2-3
Electric Specifications 2
Model
Item
DVPPS01 DVP14SS11R2/T2 DVP08SM11N DVP08SN11R/T DVP08SP11R/T DVP-16SP11R/T
Power Supply Voltage / Fuse
100~240VAC
(50/60Hz)
24VDC (-15%~10%) (has power protect with opposite pole DC input)
Input Power Operating
Characteristics
5ms or less
Maximum Power Loss Time -- 2A / 250VAC
Power Consumption -- 5W 8W
Insulation Resistance -- >5 MӨ at 500VDC (Between all inputs/outputs and earth)
Noise Immunity
ESD: 8KV Air Discharge
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS: 26MHz~1GHz, 10V/m
Grounding
The diameter of grounding wire cannot be smaller than the wire diameter of terminals L and N (All DVP units should be grounded directly to
the ground pole).
Environment
Operation: 0к~55к (Temperature), 50~95% (Humidity); Storage: -25к~70к (Temperature), 5~95% (Humidity)
Pollution degree 2
Vibration /Shock Immunity Standard: IEC1131-2, IEC68-2-6 (Test Fc) / IEC 1131-2 & IEC68-2-27 (Test Ea)
Weight (g)
210 214/208 128 154 /146 141 /136 162 /154
Input Point Electric Specification Output Point Electric Specification
Input Point Type DC (Sink or Source) Output Point Type Relay-R Transistor-T
Input Current 24VDC 7mA Current Spec. 2A/1 point (5A/COM)
55к 0.1A/1 point, 50к 0.15A/1 point
45к 0.2A/1 point, 40к 0.3A/1 point
(2A/C O M)
OFFШON Above 10VDC
Voltage Spec. Below 250VAC, 30VDC 30VDC
Active Level
ONШOFF Below 9VDC
100 VA (Inductive)
Maximum Load
120 W (Resistive)
7.2 W
Reaction Time About 10ms (Adjust D1020 and D1021 can be 0~15ms)
Reaction Time About 10ms
OFFШON 15Ӵs, ONШOFF 25Ӵs