Specifications
1 - 8 0 0 - 6 3 3 - 0 4 0 5
e11-54
Operator Interface
Volume 14
Providing power to the touch panel
1.) During operation, the panel functions in High-Power Mode when
powered by a minimum 1 Amp 12 - 24 VDC power source.
Recommended power supplies are AutomationDirect part number
PSC-24-015 or PSC-24-030.
2.) C-more Micro-Graphic STN panels EA1-S6ML and EA1-S6MLW are
powered during programming from the PC through the USB to RS-
232 Programming Cable Assembly, EA-MG-PGM-CBL.
C-more Micro-Graphic TFT panel EA1-T6CL is powered during pro-
gramming through a USB A-to-B cable such as USB-CBL-AB6.
The panel will operate in Low-power mode when powered by the
PC and result in a dim screen.*
3.) Optionally, the C-more Micro-Graphic STN panels EA1-S6ML and
EA1-S6MLW can function in Low-Power Mode powered from most
AutomationDirect PLC’s RJ12 serial communications port. Use a DV-
1000CBL communications cable, or a DV-1000CBL communications
cable with a FA-15HD 15-pin HD DSub/RJ12 Adapter connected to
most AutomationDirect PLC’s 15-pin HD communications port
(DL06, D2-250-1 & D2-260) for Low-Power operation. See Chapter 6:
PLC Communications in the Hardware User’s Manual (P/N: EA1-
MG6-USER-M) for additional details. The panel will operate in low-
power mode when powered by the PLC. The C-more Micro-Graphic
TFT panel EA1-T6CL cannot be powered from a PLC.
RR
LISTEDLISTED
7M177M17
Date code:****Date code:****
55443322
11
R01.R01.
MADE IN CHINAMADE IN CHINA
EA1-S6MLW + serial numberEA1-S6MLW + serial number
MODEL:EA1-S6MLWMODEL:EA1-S6MLW
INPUT:12-24V 6.5WINPUT:12-24V 6.5W
IND.CONT.EQ.IND.CONT.EQ.
81
15
9
Supply to Panel:
1 A @ 12 - 24 VDC
(10.8 - 26.4 VDC)
+
–
GND
Equipment
Ground
Recommended
DC Supply Fuse
750 mA fast acting,
ADC p/n AGC-75
6” Panel powered from a DC power source – wiring diagram
C-more 6” Micro-Graphic
Power Connection Wiring
EA1-S6ML or EA1-S6MLW powered from an AutomationDirect PLC
via communications cable
NOTE: Recommended DC power supply to power the C-more Micro-Graphic Panel,
AutomationDirect Part No. PSC-24-015 or PSC-24-030.
*NOTE: When the panel is powered through Port1, the screen brightness is diminished. For full
brightness, connect an external Class 2, 12-24 VDC power source to the panel’s power connection.
Low-Power Mode should be used during initial programming only. Connect an external Class 2,
12-24 VDC power source when the panel is installed in its application.
Power Supplied to Panel through Cable from AutomationDirect PLC RJ12 port:
RS-232C (p/n DV-1000CBL)
To PLC
RJ12 Port
To C-more
STN Micro-Graphic
Serial Port1
6
4
GND
TXD
1
3
GND
Wiring Diagram
3
RXD
2
+5 V
1 = Sig GND
2 = not used
3 = RXD
4 = TXD
5
= +5 VDC
6 = Sig GND
1 2 3 4 5 6
R
J12 6-pin
Phone Plug
(6P6C)
1
GND
6
GND
1 2 3 4 5 6
R
J12 6-pin
Phone Plug
(6P6C)
1 = Sig GND
2 = +5 VDC
3 = RXD
4 = TXD
5
= not used
6 = Sig GND
4
5
RXD
TXD
+5 V
10 feet [3.0 m] Maximum
INPUT:12-24V 6.5W Class2INPUT:12-24V 6.5W Class2
RR
LISTEDLISTED
7M177M17
Date code:****Date code:****
55443322
11
R01.R01.
MADE IN CHINAMADE IN CHINA
EA1-T6CL + serial numberEA1-T6CL + serial number
M
ODEL:EA1-T6CLMODEL:EA1-T6CL
IND.CONT.EQ.IND.CONT.EQ.
81
15
9
Supply to Panel:
1 A @ 12 - 24 VDC
(10.8 - 26.4 VDC)
+
–
GND
Equipment
Ground
Recommended
DC Supply Fuse
750 mA fast acting,
ADC p/n AGC-75
EA1-T6CLEA1-S6ML & EA1-S6MLW