Specifications
1-800-633-0405
B10–40
Operator Interface
C-more 6” Micro-Graphic PLC Connections
Cabling requirements
When using the built in RJ12 serial port (Port1) on the
C-more 6” Micro-Graphic panel to connect with the DL05,
DL06, DL105, DL205, D3-350 and DL405 CPUs, your
cabling choices are fairly simple.
• DV-1000CBL — connects to DL05, DL06, DL105, DL205, D3-350
and D4-450 phone jack.
• D4-1000CBL — connects to all DL405 CPU 15-pin ports.
A maximum cable length of 10 feet between the
C-more Micro-Graphic panel and the PLC is recommended
when powering the panel in Low-Power Mode from the PLC.
The C-more 6” Micro-Graphic panel can also communi-
cate through its built-in 15-pin serial port (Port2) via RS-
232, RS-422 and RS-485 using these cables.
• EA-2CBL — connects to DL05, DL105, DL205, D3-350 and D4-
450 phone jack.
• EA-2CBL-1 — connects to D2-250, D250-1, D2-260, DL06 VGA
connector.
PLC Supported Protocols
• DirectLOGIC K-sequence
• DirectNET
• Modbus (Koyo Addressing)
• Modbus RTU
• Entivity Modbus RTU
• Allen-Bradley DF1 Half Duplex
• Allen-Bradley DF1 Full Duplex
• Allen-Bradley PLC5 DF1
• Allen-Bradley DH485
• GE Fanuc SNPX (90/30, 90/70, Micro 90, VersaMax Micro)
• Omron Host Link (C200 Adapter, C500)
• Omron FINS Serial (CJ1, CS1)
• Mitsubishi Melsec FX
• Siemens PPI
C-more 6” Micro-Graphic Port 1 to DL05 PLC Port 2
C-more 6” Micro-Graphic Port 2 to DL06 PLC Port 2
Port
2
Port
2
Panel to
Direct
LOGIC
VGA 15-pin port
serial cable
p/n EA-2CBL-1
DL06 PLC
C-more 6 Inch
Micro-Graphic
Panel
DL05 PLC
Port 2
Direct
LOGIC
serial cable
DV-1000CBL
C-more 6 Inch
Micro-Graphic
Panel
Port 1
R
LISTED
LISTED
7M17
7M17
Date code:****
Date code:****
5432
1
R01.
R01.
MADE IN CHINA
MADE IN CHINA
EA1-S6MLW + serial number
EA1-S6MLW + serial number
MODEL:EA1-S6MLW
MODEL:EA1-S6MLW
INPUT:12-24V 6.5W
INPUT:12-24V 6.5W
IND.CONT.EQ.
IND.CONT.EQ.
6 5 4 3 2 1
RJ12 serial
communications Port1
Pin Signal
1 Logic GND
not used
RXD (232C)
TXD (232C)
2
3
4
5 +5 VDC
6 Logic GND
81
15
9
Pin Signal
1 Frame GND
TXD (232C)
RXD (232C)
Future
2
3
4
5Logic GND
Pin Signal Pin Signal
6LE
CTS (232C)
RTS (232C)
RXD+ (422/485)
7
8
9
10 RXD– (422/485)
11 TXD+ (422/485)
TXD– (422/485)
Term. Resistor
do not use
12
13
14
15 do not use
PLC 15-pin serial
communications Port2
RS-232 RS-232/422/485
Expansion
Connector
C-more 6” Micro-Graphic Communicaton Ports