Operating instructions
DHW
l
Open the main cold feed valve.
l
Open all hot taps to purge DHW system.
l
Check for water soundness.
Central Heating
l
Open flow and return valves on the boiler.(l9 and 23
fig. 15)
l
Open the automatic air vent (6 fig. 16)
l
Fill system and vent radiators.
l
Set system pressure and remove filling loop.
l
Check for leaks.
l
Manually check pump is free to turn.
l
Switch on electrical supply.
l
Turn selector switch (34 fig. 16) to heating only or heating
and hot water position.
l
Allow pump to run for several minutes.
Fig. 15
l
Isolate electrical supply.
l
Drain boiler and check water filter (29 fig. 2) for
installation debris.
4 Turn the heating flow temperature adjustment to maximum
(37 fig. 16).
l
The boiler will light.
1
l
Replace filter and recharge system.
Lighting the Boiler
l
Connect gas pressure gauge to test point ( 45 fig. 16).
l
Turn on the gas supply and boiler gas tap ( 21 fig. 15.
l
Ensure electrical supply is on.
l
Ensure all external controls and built clock are calling for
heat.
l
Turn selector switch ( 34 fig. 16) to heating only position.
l
Allow the boiler to heat system.
l
Check the inlet gas pressure (working pressure) while boiler
operating. (Refer to technical data).
l
Check the operation of the boiler controls and safety
devices.(see separate servicing leaflet for details)
l
Set the by pass (Refer to system guidance).
l
Re-flush the system to remove any dissolved oils and fluxes.
l
Recharge system pressure and introduce any water
treatment as required.