Operating instructions
3. Burner operating modes :
To gain access to the switches it is necessary to remove the
facia:
remove the main case
pivot the electrical box forwards
remove the pressure gauge clip noting its position
replace elecrical box in its upright position
remove the two screws and unclip the fascia from the
electrical box
remove the rubber grommet to gain access to the switches
PCB adjustments (fig. 14) :
Four switches are gathered together on the regulation PCB
and labled SW4.
3 min
3 min
TUR
Pmin
IL
/
Fig. 14
factory setting
Switch 1 TAC selects Central heating anticycling delay
either 3 min (factory setting) or 30 see
Switch 2 TIC selects delay switching from DHW to C/H
either 30 see (factory setting ) or 3 min
Switch 3 selects the modulation of the Burner.
NOR means normal modulation (off - l/3 - full on) factory
setting
TUR means Full On or Off mode
Switch 4 selects Central heating power limitation
Pmax means the boiler could provide full power for
heating - factory setting
Pmin means power for heating is limited to 113 only
When settings have been made replace the rubber grommet
and refit all components in
the reverse order.