Owner's manual

409
PM400DVA060
Intellimod™ Module
Single Phase IGBT Inverter Output
400 Amperes/600 Volts
Powerex, Inc., 200 Hillis Street, Youngwood, Pennsylvania 15697-1800 (724) 925-7272
Electrical and Mechanical Characteristics, T
j
= 25°C unless otherwise specified
Characteristics Symbol Test Conditions Min. Typ. Max. Units
Control Sector
Short Circuit Trip Level SC -20°C T
j
125°C, V
D
= 15V 650 910 Amperes
Short Circuit Current Delay Time t
off(SC)
V
D
= 15V 10 µS
Over Temperature Protection OT Trip Level 100 110 120 °C
(V
D
= 15V, Lower Arm) OT
r
Reset Level 85 95 105 °C
Supply Circuit Under Voltage Protection UV Trip Level 11.5 12.0 12.5 Volts
(-20°C T
j
125°C) UV
r
Reset Level 12.5 Volts
Circuit Current I
D
V
D
= 15V, V
CIN
= 5V, V
N1
-V
NC
—2330mA
V
D
= 15V, V
CIN
= 5V, V
P1
-V
PC
—2330mA
Input ON Threshold Voltage V
CIN(on)
Applied between 1.2 1.5 1.8 Volts
Input OFF Threshold Voltage V
CIN(off)
C
P1
-V
PC
, C
N1
-V
NC
1.7 2.0 2.3 Volts
Fault Output Current I
FO(H)
V
D
= 15V, V
FO
= 15V* 0.01 mA
I
FO(L)
V
D
= 15V, V
FO
= 15V* 10 15 mA
Minimum Fault Output Pulse Width t
FO
V
D
= 15V* 1.0 1.8 mS
SXR Terminal Output Voltage V
SXR
T
j
125°C, R
in
= 6.8k (S
PR
, S
NR
) 4.5 5.1 5.6 Volts
* Fault output is given only when the internal SC, OT, and UV protections circuits of either an upper-arm or a lower-arm device operate to protect it.