SECTION 2 - STORAGE and SHELF LIFE
2.1 Storage of VRLA (valve regulated lead acid) Batteries
Store batteries indoors, preferably at 77°F (25°C) or in a cool 20°F to
90°F (-7°C to 32°C), dry location and place on charge by the
date
found on the battery carton.
Note:
Batteries that are not placed in service for several months will
self-discharge.
Storage time is based on storage at 77°F (25°C) and is six months for
Liberty Series
1000
valve regulated cells. Do not allow the electrolyte
to freeze, as this will destroy the battery and can cause a potentially
hazardous condition and leakage.
Refer to Table 1, for electrolyte freezing temperatures. Although the
specific gravity of a fully charged battery may present no freezing
prob
lem, a discharged battery gravity may freeze at relatively mild
temperatures.
TABLE 1 - FREEZING TEMPERATURE VS SPECIFIC GRAVITY
Specific Gravity Freezing Temperature
at 77°F (25°C)
Celsius
F
ahrenheit
1.000
0.0 +32
1.050
-3.3 +26
1.100 -7.7 +18
1.150 -15 + 5
1.200
-27 -17
1.250 -52 -61
1.300 -70 -95
1.350
-49 -56
1.400 -36 -33
Note: Store cells upr
ight in order to maximiz
e electrolyte contact with
the plates.
2.2 Stora
g
e limitations
C&D Technologies Liberty Series 1000valve-regulated (sealed) lead