FV/Time Models 1 hr. 3 hr. 5 hr. 8 hr. 10 hr. 20 hr.
FAM 12-100 66.3 28.1 18.5 12.4 10.2 5.5
1.75 FA 12-125 86.3 37.1 24 15.8 12.9 6.8
FAM 12-150 99.9 43 28.1 18.8 15.4 8.2
FAM 12-100 64.7 27.6 18.2 12.3 10.1 5.4
1
.80
F
A 12-125 83.2 35.8 23.2 15.4 12.6 6.6
F
AM 12-150 96.2 42.4 27.8 18.6 15.3 8.1
FAM 12-100 1 hr 3 hr 5 hr 8 hr 10 hr 20 hr
1.84 FA 12-125 78.7 34 22.2 14.7 12.1 6.4
FAM 12-150 92.4 41.7 27.5 18.4 15.1 8
FAM 12-100 57.6 25.3 16.7 11.3 9.3 5
1.88 FA 12-125 72.8 31.6 20.7 13.8 11.3 6
FAM 12-150 92 41.2 27.3 18.3 15 8
FAM 12-100 55.1 24.3 16.1 10.9 9 4.8
1.90 FA 12-125 69.1 30.1 19.7 13.2 10.8 5.8
FAM 12-150 85.3 40.4 27 18.2 14.9 7.9
Ratings in Amperes at 77°F (25°C)
10
C&D Front Access products meet or exceed IEEE-485 at time of shipment.
Additional rates are available at www.cdstandbypower.net