SECTION 3 - INSTALLATION AND ASSEMBLY
1.3.1 Installation
Liberty
®
Series 1000 FAM and FA batteries are best installed horizontal-
ly. Physical dimensions for layout may be found in Table 1. Install battery
in a cool, dry location away from heat sources. The recommended oper-
ating temperature (ambient) is 65-77°F (18-25°C). The allowable tem-
perature range with performance degradation at the extreme tempera-
tures is 32-90°F (0-32°C). Float voltage compensation should be made
for temperatures other than 77°F (25°C).
NO
TE:
Units connected within a batter
y string are connected in
series positive post to negative post to positive post, etc.
If possible the application should allow at least 3/8 of an inch
betw
een batteries for proper inter-connection spacing and air circula
-
tion. When handling units ne
ver lift them by the terminals as this can
damage the post seals and cause acid leakage.
Avoid sources of hot or cold air directed on a section of the battery
that could cause temperature variations within the battery assembly.
Such v
ar
iations will compromise optimum battery performance such
as float voltages of individual cells.