TECHNICAL BULLETIN 41-6965 Condensed Installation & Operating Procedures 41-6965/0512/CD www.cdtechno.
electrically conductive and is corrosive. If electrolyte contacts the skin, wash immediately and thoroughly. If electrolyte enters the eyes, also seek medical attention. Neutralize spilled electrolyte with a solution of 1 lb. bicarbonate of soda (baking soda) to 1 gallon of water. I. BATTERY DESCRIPTION The valve regulated lead acid (VRLA) battery is a minimal maintenance system, which utilizes an oxygen recombination cycle to minimize gassing and eliminate electrolyte maintenance.
V. INSTALLATION INSTRUCTIONS Typically individual batteries are connected in series to form a higher voltage string of batteries (e.g. 4 each 12 volt batteries connected in series for a 48 volt battery system). Two or more strings may then be connected in parallel to increase the total capacity of the system (e.g. two strings of 48 volt 75 ampere hour batteries connected in parallel for 48 volts at 150 ampere hours capacity).
The following maintenance schedule should be followed: Annually • Repeat the semi annual checks. • Retorque all inter unit connecting hardware per table 1. • Perform inter unit connector resistance checks. Quarterly • • Check pilot units temperature at the negative terminal. Measure and record the system float charging voltage. IX. PERFORMANCE TESTS • Measure and record the individual units float charging voltage. Semi Annually • Repeat the quarterly checks.
« « « « « « « « « « « « « « « « « « «« « « « « « « « « « « « « « « « « « « « « « « « « B &,5&8,7 %5($.(5 FIGURE 1-SINGLE STRING 48 VDC BATTERy « « « « « « « « « « « « « « « « « « « « « « « § « « FIGURE 2-SINGLE STRING 48 VDC BATTERy « « « « « « « « « « « « « « « « « «« « « « « « « « « « « « « « « « « « « « « « « « « -81&7,21 %2; « « « B / / / / &,5&8,7 %5($.