Instructions

29
2. Conguration Maintenance Timer/Counter (TIME, COUNT)
Alternatively,theinputcanalsobeusedtocountalongoperatinghoursandactivationnumbers.Observe:
• Astartingvalueforbothversionsisspeciedbytextmessageandcounteddown.Alarmistriggeredat„0“.
• Only switching times in excess of 3 seconds are securely recognised.
• Everyankiscounted(L->H,H->L).
• Thetimeronlycountsfullsecondsandmayhaveadelayofupto3secondsperswitchingank.
Thefollowingcommandservestoactivatethisfunction:
SET <IN1/IN2/…/INn> <TIME/COUNT> <starting value> [INV] #1513
TIME: Secondscountingdown
COUNT: Activationcounter,countsateachank
INV: CanonlybeusedforTIME;countsforLOW,otherwiseforHIGH
StartingvalueTIME: 0to33,554,431seconds
StartingvalueCOUNT: 1to1,048,575LH-/HL-transfers
Examples:
SET IN1 COUNT 4 #1513
Thealarmistriggeredforthe4thswitchingprocess.
SET IN3 TIME 55 INV #1513
Thealarmistriggeredafteratleast55secondsinthedeactivatedcondition.
ThecurrentcounterstatuscanusuallybedeterminedwiththeTESTINx-command.
AllINx-functionsareresettofactorysettingswiththecommand:
RESET <IN1/IN2/…/INn> #1513
Therecognitionofthisstatuschangehasadelayof+1s.Foreachswitchingoperationthiserrorwilladd.