B-Box HV Installation Guide
BYD Battery-Box HV User Manual 
6 Cleaning and Maintenance 
6.1 Cleaning 
It is recommended that the BYD Battery-Box HV system be cleaned periodically. If the enclosure is dirty, please use                                     
a soft,dry brush or a dust collector to remove the dust. Liquids such as solvents, abrasives or corrosive liquids                                     
should not be used to clean the enclosure. 
6.2 Maintenance 
6.2.1 Recharge Requirements During Normal Storage 
Batteries should be stored in an environment with a temperature range between -10℃~+45℃, and maintained                             
regularly according to the following table with 0.5C (12.5A) current until 40% SOC after a long time of storage. 
Recharge conditions when in storage 
Storage environment 
temperature 
Relative humidity of storage 
environment 
Storage time 
SOC 
Below -10℃ 
/ 
prohibit 
/ 
-10~25℃ 
5%~70% 
≤12 months 
30%≤SOC≤60% 
25~35℃ 
5%~70% 
≤6 months 
30%≤SOC≤60% 
35~45℃ 
5%~70% 
≤3 months 
30%≤SOC≤60% 
Above 45℃ 
/ 
prohibit 
/ 
6.2.2 Recharge Requirement When Over Discharged 
Please recharge the over discharged batteries in a timeframe that is in accordance to the following table, otherwise                                   
the over discharged battery modules will be damaged. 
Recharge conditions when battery is over discharged 
Storage Environment Temperature 
Time Before Recharge is Necessary 
-10~25℃ 
≤15 days 
25~45℃ 
≤7 days 
8 