Personnel Alert: Base Station
Alarm Relay Contact Wiring and Configuration
Table 13. Alarm Circuits and Switch Positions for the
S1 Dip Switch
Alarm Circuits
Switch
Positions
Open (NO) or
Closed (NC)
Low
L
High
H
System
S
Manual Alarm Test Settings
aWarning
If the area is classified, the base station must
be deenergized before testing alarm contacts.
Connect each alarm circuit to the positions marked on the
removable 6-wire screw down connector on the radio board.
Figure 14. Alarm Relay Contact Wiring
23