6 Reduction of the connection load (derating)
Pos: 25 / #Ne ustr u ktur# /Onl in e-Do kume ntati on (+ KN X)/Der ati ng /Der ati ng - Di m mer ( Lei stu ngs mind eru ng 20 pr oze nt bei Ein bau i n Gasb et on .. .) @ 2 0\mod_1327310948240_15.docx @ 137093 @ @ 1
The dimmer heats up during operation because part of the connected load is lost and converted into heat. The
specified rated power is designed for dimmer installation in a solid masonry wall.
When installing the dimmer in a wall made of gas concrete, wood, or plasterboard, the maximum connection load
must be reduced by 20%.
The connected load must always be reduced when several dimmers are installed one below the other or when
other heat sources cause additional heating. In intensely heated-up rooms, the maximum connected load must be
reduced according to the diagram.
Pos: 26 / #Ne ustr u ktur# /Onl in e-Do kume ntati on (+ KN X)/Der ati ng /Der ati ng - Kur ve -- 35-70 -- Kur ve @ 1 9\mod_1311948779960_15.docx @ 108276 @ @ 1
Fig. 1: Derating