Price - $3.00 INSTALLATION, OPERATING AND SERVICE INSTRUCTIONS FOR V7 SERIES OIL FIRED BOILER KNOCKDOWN & PACKAGED HEATING UNITS These instructions have been reviewed by ULC and found suitable for use in the installation of ULC labeled V-7 Series Boilers. As an ENERGY STAR® Partner, Burnham Corporation has determined that the V73WR (0.60 GPH), V74WR (0.80 GPH), V75WR (0.90 GPH), and V76WR (1.
IMPORTANT INFORMATION - PLEASE READ THIS PAGE CAREFULLY 1. THIS BOILER HAS LIMITED WARRANTIES, COPIES OF WHICH ARE PRINTED ON THE BACK COVER OF THIS MANUAL. 2. THIS BOILER IS SUITABLE FOR INSTALLATION ON COMBUSTIBLE FLOORING. BOILER CANNOT BE INSTALLED ON CARPETING. 3. ALL BOILERS MUST BE INSTALLED IN ACCORDANCE WITH NATIONAL, STATE AND LOCAL PLUMBING, HEATING AND ELECTRICAL CODES AND THE REGULATIONS OF THE SERVING UTILITIES WHICH MAY DIFFER FROM THIS MANUAL.
IMPOR TANT Before starting to in stall this oil bo iler, read these in structio ns carefu lly. Keep instruction s in legible condition and po sted n ear oil boiler fo r reference by owner an d service technician . TABLE OF CONTENTS I. II. III. IV. V. VI. General Information ............................. 3 Knockdown Boiler Assembly ............... 7 Installation Instructions ...................... 12 Operating Instructions ........................ Boiler Cleaning ..................................
Figure 1B: V73 thru V79 Water Boiler with Tankless Heater (WBT) Figure 1C: V73 thru V79 Steam Boiler with or without Tankless Heater ("SBT" or "SB") 4
Βυρνηαµ Figure 1D: V713 and V714 Packaged Water Boiler Less Tankless Heater (WB) Burnham Figure 1E: V713 and V714 Packaged Water Boiler with Tankless Heater (WBT) 5
A. INSPECT SHIPMENT carefully for any signs of damage. 2. FOR BASEMENT INSTALLATION, provide a solid base, such as concrete, if floor is not level, or if water may be encountered on floor around boiler. 1. ALL EQUIPMENT is carefully manufactured, inspected and packed. Our responsibility ceases upon delivery of crated boiler to the carrier in good condition. 3. PROVIDE SERVICE CLEARANCE of at least 24” on right side of boiler for removal of rear tankless heater.
SECTION II: KNOCKDOWN BOILER ASSEMBLY Note: If Boiler is Packaged Go To Section III section as shown in Fig. 3. Place gaskets so as not to allow any flueway blockage. A. REMOVAL OF BARE BOILER FROM SKID 1. Boiler is secured to base with 4 bolts, 2 on front and 2 on rear, see Figure 2. Remove all bolts. 2. Cut the remainder of the roll into two (2) equal pieces. Place each piece along the sides, allowing the ends to overlap the front and rear pieces. 2. Tilt boiler to right and to rear.
Figure 4: Boiler Tapping Locations and Usage (Knockdown Boilers Only) PU R P O SE O F TA PP IN G S Ta p p in g L o ca tio n S te a m B o ile r S ize N o n -H e a te r W a te r B o ile r w /H e a te r N o n -H e a te r F ro n t H e a te r R e ar H e a te r L 81 48A O p era tin g C on tr ol L81 24 C O p era tin g C on tr ol F lus h Plu g A ¾" PA 4 04A P r es su retro l (P r obe LW C O ) P lugg ed (F lo at LW C O ) B ¼" P re ss ure /Va cu um G aug e Tem p era tu re/P re ss ur e G aug e C ¾"
Figure 5: Knockdown Boiler Jacket Assembly b. Tapping “M” —Install ¾” x 8” long nipple into ¾” tapping located next to front section top supply tapping — all boiler sizes. I. side panel mounting holes with the front and rear panel holes. Secure with #8 x ½” long sheet metal screws. INSTALL FLUSH JACKET (See Figure 5). 5. Install jacket top panel. Place jacket top panel on boiler and secure to front, rear and left side panels with #8 x ½” long sheet metal screws. 1.
Figure 6 burner to the left. Install two remaining 5/16” x ½” long bolts in horizontal sets of holes. Level burner and fully tighten all bolts. manner as rating label. c. On steam boilers, install the Lowest Permissible Water Level Plate, Form No. 1204 (shipped in Steam Trim Carton), on the jacket right side panel. Align the two holes in the plate with the two 1/8” dia. holes located near the front edge, in line with the lower sight glass tapping, and secure with #8 x ½” lg. sheet metal screws. J. K.
the sight glass using the two ½” tappings to the right of the probe LWCO. 4. Screw drain valve into 1½” tapping in lower rear section using 1½” x ¾” bushing (note - lower front section tapping “G” (see Figure 4) is used for standard return on water boilers). 5. Install float-type Low Water Cutoff, if so equipped. See Figure below. a. Install nipples and unions in Tappings D. b. Mount hardware to low water cutoff body. Install assembly. c.
SECTION III: INSTALLATION INSTRUCTIONS 4. Packaged boilers with Probe style LWCO. Install Limit in Tapping A using ¾ NPT x 2" nipple, ¾ NPT elbow, ¾ NPT x ¼ NPT bushing, and syphon included in trim bag. See Figure on previous page. Connect wiring harness from Low Water Cutoff. See Figure below. A. REMOVE CRATE — (Packaged Boilers) 1. Remove all fasteners at crate skid. 2. Lift outside container and remove all other inside protective spacers and bracing.
TS-39-17-D Fig 8: V73 Thru V79 Recommended Boiler Piping For Gravity Return Steam Boiler TS-39-4-C Fig.
In order to insure long product life, oxygen sources should be eliminated. This can be accomplished by taking the following measures: 1. Repairing system leaks to eliminate the need for addition of make-up water. 2. Eliminating open tanks from the system. 3. Eliminating and/or repairing fittings which allow oxygen absorption. TS-O-62-B 4. Use of non-permeable materials in the distribution system. 5. Isolating the boiler from the system water by installing a heat exchanger. F.
TABLE 3: TANKLESS HEATER DATA: Rear Mounted Heater on Steam and Water Boilers Boiler Model Heater No. Heater Rating (GPM) WARNING Install an automatic mixing valve at the tankless heater outlet to avoid risk of burns or scalding due to excessively hot water at the fixtures. Adjust and maintain the mixing valve in accordance with the manufacturer's instructions. Pressure Drop thru Heater (PSI) Steam Water Steam Water V713 V1-2 --- 3.25 --- 5.6 V73 V1-2 2.75 3 3.9 4.7 V1-1 --- 3.
Fig. 14: Proper and Improper Locations of Draft Regulator Fig. 13: Recommended Smokepipe Arrangement and Chimney Requirements 3. For the same reasons as in (2.) above, heat extractors mounted into the breeching are not recommended. requires less fuel to be burned and sends less heat up the chimney. H. INSTALL ELECTRIC WIRING in accordance with National Electrical Code and local regulations. A separate ELECTRICAL CIRCUIT should be run from meter with a Fused Disconnect Switch in the Circuit.
TABLE 4: SINGLE-STAGE UNITS (3450 RPM) TWO-PIPE SYSTEMS Lift "H" (See Fig. 16) Figure 15 IMPORTANT Single-pipe installations must be absolutely airtight or leaks or loss of prime may result. Bleed line and fuel unit completely.
Fig. 17: Wiring Diagram for Steam Boilers with Standard Hydrolevel CG-450 Probe LWCO, Beckett AFG Burner and Controls, with or without Tankless Heater Fig. 18: Wiring Diagram for Steam Boilers with Optional McDonnell & Miller PS-801 Probe LWCO, Beckett AFG Burner and Controls, with or without Tankless Heater BOILER SEQUENCE OF OPERATION WITH PROBE LWCO When the thermostat calls for heat, it energizes the cad cell primary control, bringing on the burner.
TS-39- -C Rev. O Fig. 19: Wiring Diagram for Steam Boilers with Optional McDonnell & Miller PS-804-120 Probe LWCO, Beckett AFG Burner and Controls, with or without Tankless Heater NOTE: The McDonnell Miller low water cut off incorporates a 10 second delay to prevent nuisance burner cut-off due to rapid water level fluctuations. The LWCO also has a time delay of 15 seconds which allows additional fill time after water touches the probe. Red LED indicates a low water condition. Fig.
Fig. 21: Wiring Diagram for Water Boilers with Beckett AFG Burner and Controls, without Tankless Heater SEQUENCE OF OPERATION A call for heat by the thermostat energizes the L8148A control which in turn energizes the R4184D primary control to turn on the burner. If burner ignites within approximately 45 seconds and the cad cell sees flame, the burner will continue to operate until the call for heat is satisfied or the setting of the high limit is reached.
SECTION IV: OPERATING AND SERVICE INSTRUCTIONS WARNING All boilers equipped with burner swing door have a potential hazard which can cause severe property damage, personal injury or loss of life if ignored. Before opening swing door, turn off service switch to boiler to prevent accidental firing of burner outside the combustion chamber. Be sure to tighten swing door fastener completely when service is completed.
NOTICE Burner-specific references in the follow ing instructions pertain to the Beckett AFG , supplied as standard equipment.
(Non-Burnham Drawing, Copy from LE Manual, 81433010R4, Page 13, without "Figure 12A, 12B, 12C and 12D"; sample enclosed) Fig. 24: "L1" and "V1" Head Electrode Positioning and Gun Setting (Beckett AFG) 5. TURN “OFF” BURNER and remove pressure gauge. Install gauge port plug and tighten. Start burner again. 6. CAD CELL LOCATION AND SERVICE The burner is supplied with a cadmium sulfide flame detector mounted at the factory, mounted on the bottom of the ignitor. See Figure 25.
CAD CELL TEST g. Open line switch. Clean cell face and see that cell is securely in socket. Reconnect leads. Reset safety switch. h. Close line switch. If burner starts and runs beyond safety switch cut-out time, cell is good. If not, install new cell. K. CHECK FOR CLEAN CUT OFF OF BURNER. 3. WARNING — Check High Limit Control — Jumper Thermostat Terminals. Allow burner to operate until shut-down by limit. Installation is not considered complete until this check has been made. 1.
d. Dismount the low water cutoff control from the probe. required. Examine all visible wiring for brittle or worn insulation and make sure electrical contacts are clean and that they function properly. Give special attention to solder joints on bellows and float when this type of control is used. Check float for evidence of collapse and check mercury bulb (where applicable) for mercury separation or discoloration. Do not attempt to repair mechanisms in the field.
v. Continue this slow boiling and trickle of overflow for several hours until the water coming from the overflow is clear. iv. Stop burner and drain boiler in a manner and to a location that hot water can be discharged with safety. v. Refill boiler to normal water line. If water in gauge glass does not appear to be clear, repeat steps (i. thru iii.) and boil out the boiler for a longer time. b.
recommended boil out compound. and can vary from sample to sample. For all of those reasons a spare nozzle is a desirable item for a serviceman to have. iii. Replace safety relief valve. iv. Fill the entire system with water. v. 2. FLAME SHAPE — Looking into the combustion chamber through the observation door, the flame should appear straight with no sparklers rolling up toward the crown of the chamber.
clean water to prescribed water level. IMPORTANT 4. Always keep the manual fuel supply valve shut off if the burner is shut down for an extended period of time. SUCTION LINE LEAKS - THE OIL MUST BE FREE OF AIR. Try bleeding the pump through a clear tube. There must be no froth visible. There are various test kits available to enable you to look at the oil through clear tubing adapted to the supply line at the pump fitting. Air eliminators are on the market that have potential.
(Non-Burnham Drawing Copy from other Manual) AQUASTAT SWITCHING ACTION WITHIN L8124C CONTROL The switching action within the L8124C control has three settings: 1. high limit 2. low limit 3. adjustable differential EXAMPLE: Set point of 140°F; differential set at 25°F. On a temperature rise, R-B will break and R-W will make at 155°F. On a temperature fall, R-B will make and R-W will break at 130°F. Set low limit indicator at the minimum temperature recommended for domestic hot water supply.
smokepipe, burner mounting plate, burner swing door and all flue plates are secured in place. 1. Install the canopy taking care to align the gaskets without blocking the flueways. If gasket is damaged, replace as needed. 2. Reinstall flue plates, making sure gasket on each plate is in place and forms gas tight seal. If damaged replace as needed. 3. Reinstall jacket top panel and secure with sheet metal screws. Replace jacket upper right side access panel. 4.
SECTION VI: REPAIR PARTS All V7 Series Repair Parts may be obtained through your local Burnham Wholesale distributor. Should you require assistance in locating a Burnham Distributor in your area, or have questions regarding the availability of Burnham products or repair parts, please contact your Burnham Regional Sales Office as listed below. B urnh am Corpo rati on Regional Offices A. Burnham Corporation - Central & Western Regions P.O.
BARE BOILER ASSEMBLY
Item No. Description Part No. V72 V713 V73 V714 V74 V75 V76 V77 V78 V79 BARE BOILER ASSEMBLY (See Page 32 for Illustration) Front Section (Non-Htr.), Machined Water 71727019 1 --- 1 --- 1 1 1 1 1 1 Front Section (Non-Htr.), Machined Water 71727015 --- 1 --- 1 --- --- --- --- --- --- Front Section (Non-Htr.), Machined Steam 71727018 --- --- 1 --- 1 1 1 1 1 1 2 Front Section w/Htr.
BARE BOILER ASSEMBLY (CONTINUED)
CONTINUED FROM PAGE 33 Item Description No. Part No.
TS-39-112-D V713 and V714 FLUSH JACKET
Item No. Description Part No.
TS-39-109-D V72 Thru V79 FLUSH JACKET
Item No. Description Part No. V72 V73 V74 V75 V76 V77 V78 V79 V72 Thru V79 Flush Jacket Components - Items 1 thru 7 Include Insulation As Part of Ass'y Jacket Front Panel Ass'y w/o Htr. Opg. (Wtr. Blr.) 60427090 1 Jacket Front Panel Ass'y w/o Htr. Opg. (Stm. Blr.) 60427091 --- Jacket Front Panel Ass'y w/Htr. Opg. (Wtr. Blr.) 60427092 --- Jacket Front Panel Ass'y w/Htr. Opg. (Stm. Blr.) 60427094 --- 1 1 2 Plastic Collar Extension-Jkt. Frt. Panel w/Htr. Opg.
V73 Thru V79 STEAM BOILERS - TRIM AND CONTROLS
Item No. Description Part No. V73 V74 V75 V76 V77 V78 V79 V73 Thru V79 STEAM BOILERS - TRIM AND CONTRO LS (See Page 40 for Illustration) 1. Draft Regulator 1A DR-6 Draft Regulator 8116029 1 1 1 1 --- --- --- 1B DR-7 Draft Regulator 8116001 --- --- --- --- 1 1 1 8142711 1 1 1 1 1 1 1 2.
V72 Thru V79, V713 and V714 WATER BOILERS - TRIM AND CONTROLS
ITEM DESCRIPTION NO. Part No. V72 V713 V73 V714 V74 V75 V76 V77 V78 V79 V7 2 Thru V79, V713 and V7 14 WATER BO ILERS - TRIM AND CO NTROLS (See Page 42 for Illustration) 1. DRAFT REGULATO R 1A DR-6 Draft Regulator 8116029 1 1 1 1 1 1 1 ---- ---- ---- 1B DR-7 Draft Regulator 8116001 ---- ---- ---- ---- ---- ---- ---- 1 1 1 8142711 1 1 1 1 1 1 1 1 1 1 2.
Beckett AFG Burner
BECKETT OIL BURNER PART NOS. FOR V7 SERIES BOILERS NOTE: When ordering parts always give the serial and model numbers shown on the boiler and burner. Also provide the name of the part(s) and part number as listed below. Boiler Model V72 V713 V73 V714 V74 V75 V76 V77 V78 V79 Air Tube Combination AFG70MB AF72YH AF44XN AF72YY AF44WH AF44RA AF44XO AF72WK AFG50MD AFG50MD Beckett's Spec No.
Print word document 46