Data Sheet
Webster Burner Equipment
Equipment Fuel Description
Control Cabinet Gas, #2 Oil, Gas/#2 Oil NEMA 1A with hinged door.
Control Voltage Transformer Gas, #2 Oil, Gas/#2 Oil Included with all but 115/60/1 burners.
Motor Starter Gas, #2 Oil, Gas/#2 Oil Contactor on all single phase motors. Magnetic starter with overload protection on 3
-
phase motors.
Fusing Gas, #2 Oil, Gas/#2 Oil Control circuit only.
Ignition Gas and Gas/#2 Oil Gas/Electric pilot.
#2 Oil Direct spark.
Gas, #2 Oil, Gas/#2 Oil Four [power on, fuel on, flame failure, and call for heat]
Full Mod Four [power on, fuel on, flame failure, and call for heat]
Gas,#2 Oil, Gas/#2 Oil All models.
#2 Oil C-70 and larger
Gas Train Gas and Gas/#2 Oil
UL gas train for minimum inlet pressure indicated on Burner Information table.
Shipped unassembled and consisting of the following:
z Manual shut-off valve.
z Gas pressure regulator
z Manual leak test valve.
z
A
utomatic gas valve: Diaphragm type with On-Off sequence. Solenoid typ
e
all others.
z Safety gas valve: Solenoid type.
z High and Low gas pressure switches: Models C-60 and larger.
Oil Pump #2 Oil and Gas/#2 Oil Integral with burner.
Pilot Gas Controls Gas, #2 Oil, Gas/#2 Oil All models with gas/electric pilot have manual pilot shut-off valve, soft seat low gas
pressure regulator and solenoid gas valve.
Fuel Changeover Gas/#2 Oil Manual switch.
7/10
Signal Lights
Air Flow Safety Switch
C SERIES