User guide
65
1. GENERAL – “Inspection should be conducted
annually.Serviceasfrequentlyasspeciedin
paragraphs below.” While service or maintenance is
being done, Electrical Power and all Gas Supply to the
Boiler must be “off”.
CAUTION
2. VENT SYSTEM – Vent system should be checked
annually for:
a. obstructions
b. accumulations of soot
c. deterioration of vent pipe or vent accessories due to
condensation or other reasons
d. proper support – no sags, particularly in horizontal
runs
e. tightness of joints
Remove all accumulations of soot with wire brush
and vacuum. Remove all obstructions. Replace
all deteriorated parts and support properly. Seal all
joints. See Fig. 57.
SECTION V – SERVICE
3. CLEANING OF FLUES AND BURNERS – Flue
passageways in the boiler sections should be checked
annually for any blockage or accumulation of soot.
Toobtainaccesstotheuecleanoutpanels,which
are installed on both the front and rear of the boiler,
the upper front and upper rear jacket panels must be
removed, see Fig. 55. Also remove front vestibule
panel.SeeFig.20.
FIG. 55
REMOVAL OF JACKET FRONT PANEL
DANGER
WARNING
instruction manuals.